Maximum load of refrigerant permitted in one room: internal unit
Length of the pipes
(m)
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
• Table 2
The maximum load of refrigerant in a room must be compliant with what follows:
And must not be lower than
Acronym
m
max
LFL
A
h
0
SF
- Systems with a load of refrigerant <1,842 kg are not subject to minimum area requests.
- Loads exceeding 2,22 kg are not accepted (maximum length of the pipes equal to 30m).
Only for 8/10kW units.
EN - 14
Load of refrigerant
(kg)
1.650
1.688
1.726
1.764
1.802
1.840
1.878
1.916
1.954
1.992
2.030
2.068
2.106
2.144
2.182
2.220
m
=
2,5 x (LFL)
(5/4)
max
SF x LFL x h
m
=
max
Is the maximum allowed load of refrigerant in the system in kg
Is the lower flammability in kg/m
Is the room area in m
2
Is the release height, the vertical distance in (m) from the floor to the release
point when the appliance is installed
Is a safety factor with a value of 0,75
A
(m
)
2
roomMIN
H=1100mm
-
-
-
-
-
-
8,93
9,30
9,67
10,05
10,43
10,83
11,23
11,64
12,06
12,48
x h
x (A)
1/2
0
x A
0
Description
3
A
(m
)
2
roomMIN
H=1800mm
-
-
-
-
-
-
4,53
4,62
4,71
4,81
4,90
4,99
5,08
5,17
5,26
5,36