K = nombre de pompes actives (k > 1)
Pr = pompe prioritaire
• Si K - Pr > 0
P02 (Effective Required Value) = P01 (Required Value) + (K–Pr) * P58 (Actual Value
Increase)
• Si K - Pr = 0
P02 (Effective Required Value) = P01 (Required Value) + P58 (Actual Value Increase) - P59
(Actual Value Decrease)
Calcul de la valeur requise effective en cascade, mode synchrone (MSY)
K = nombre de pompes actives (k > 1)
• Si K > 1
P02 (Effective Required Value) = P01 (Required Value) + (K–1) * P58 (Actual Value Increase)
• Si K = 1
P02 (Effective Required Value) = P01 (Required Value) + P58 (Actual Value Increase) - P59
(Actual Value Decrease)
Comportement de P58 (Actual Value Increase) et P59 (Actual Value Decrease)
• Si P58 (Actual Value Increase) = P59 (Actual Value Decrease) → Pression constante,
indépendamment du nombre de pompes en fonction.
• Si P58 (Actual Value Increase) > P59 (Actual Value Decrease) → Hausse de pression en cas
de démarrage d'une pompe secondaire.
• Si P58 (Actual Value Increase) < P59 (Actual Value Decrease) → Baisse de pression en cas
de démarrage d'une pompe secondaire.