Initial start-up
Configuration data
Air adjustment
Burner power
kW
Burner
18
P1.40 L(SV)
34
43
20
P1.60 L(SV)
37
54
45
P1.105 L(SV)
75
96
72
P2.130 L(SV)
96
117
Bold : Delivery setting; 1kg fuel-oil at 10°C = 11.86kWh
The above adjustments are basic
adjustments. With these settings,
normally, the burner can be started up.
The adjustment must then be verified
using a combustion analyser.
It may be necessary to perform
corrections subject to the single plant.
B
P 1.40 L
58
Nozzle
Fuel-oil flow
60°/80°S
kg/h
Gph (Danfoss)
0,40
1,5
0,65
2,9
0,85
3,6
0,45
1,7
0,75
3,1
1,10
4,6
1,00
3,8
1,50
6,3
2,00
8,1
1,50
6,0
2,00
8,1
2,50
9,8
Favourable combustion values can be
obtained using the
following nozzles:
DANFOSS H÷S 80°÷60°
DELAVAN W 60°
STEINEN S 60°
Air adjustment (A)
Loosen the screw using an Allen key:
•
turning the shutter clockwise
increases the flow rate;
•
turning it anti-clockwise decreases
the flow rate.
Fix the screw once the desired value
has been reached.
B
P 1.60/2.130 L
07/2014 - Art. Nr. 4200 1057 7200
Pump pressure
Firing head setting
bar
mm
12,0
1,5
12,0
2,5
12,0
3,0
11,5
0,0
12,0
1,0
12,0
4,0
11,0
1,0
12,0
2,5
12,0
5,0
10,5
0,0
12,0
1,5
12,0
2,5
Adjusting the combustion head (B)
Intervene on the screw shown in the
picture:
•
turn it using an Allen key until the
desired value is reached (index from
0 to 4.5).
Air flap position
1,8
3,5
4,5
0,9
2,5
5,0
2,5
6,0
9,0
1,5
3,5
9,0