Initial start-up

Burner adjustment

Light oil pressure adjustment

Pericolo di deflagrazione:
durante le operazioni di
regolazione, verifi care
costantemente le emissioni di
CO, CO 2 e l'indice di fumosità. In
presenza di formazioni di CO
modi ficare i valori della
combustione. Il valore massimo di
CO non deve superare i 50ppm.
Burner start-up
Prior to starting up the burner, load all
the pipes until the light oil filter fills up.
Subsequently, start the burner by
intervening on the boiler thermostat. To
completely remove the air from the light
oil pipes, loosen the relief screw on the
light oil filter during the pre-ventilation
SUNTEC 
AS V 47 A
Y1
4
3
P
V
SUNTEC
SUNTEC
1
2
1
intake connection
2
return connection
3
pressure connection
4
oil manometer connection
5
low-pressure manometer
connection
6
light oil pressure adjustment
10
solenoid valve electrical connection
Y1
light oil solenoid valve
Operation check
-
A flame monitoring safety check
must be effected during the initial
start-up phase and after servicing or
prolonged periods of inactivity of the
plant.
-
Start-up attempt with dimmed flame
detector: once the safety time
expires, the control programmer must
shift to anomaly.
-
Start-up attempt with lit up flame
detector: after 10 seconds of pre-
aeration, the control programmer
phase. During the course of this
operation, make sure that the
depression does not exceed 0.4 bar.
When light oil leaks out without bubbles
and the filter is entirely filled with light
oil, close the relief screw again.
Burner power adjustment
Adjust the light oil pressure so that
the burner dispenses the desired
power, by intervening on the pressure
regulator. Always check the
combustion values (CO, CO2,
smoke-developed index). If
necessary, modify the air flow rate in
a gradual manner.
DANFOSS 
BFP 21 R3
10
Y1
5
6
6
P
-
+
2
must shift to anomaly.
-
Normal start-up: when the burner is
functioning, dim the flame detector:
after a new start-up and once the
safety time expires, the control
programmer must shift to anomaly.
07/2014 - Art. Nr. 4200 1057 7200
Optimisation of combustion values
In the event of unsatisfactory
combustion values, modify the position
of the combustion head. This will modify
the start-up pattern and combustion
values. If necessary, compensate the
variation of the air flow rate by adjusting
the air shutter.
Caution: in case of installation on a
boiler, observe the minimum flue gas
temperature according to the
indications of the boiler
manufacturer and the requirements
of the flue gas discharge system, so
as to avoid condensate build-up.
Light oil pressure adjustment
To adjust the light oil pressure (and thus
the burner power), intervene on the
pressure regulator 6 on the pump.
Turn towards:
-
the right: pressure increases;
-
the left: pressure decreases;
10
Check the value by connecting a
manometer to fitting 4, thread R1/8".
Depression check
3
The vacuum gauge for measuring
P
depression must be connected to fitting
4
5, R1/8".
5
Maximum allowed depression 0.4 bar.
V
With higher depression values, the
heating oil gasifies causing a
screeching sound and damage to the
pump.
1
Cleaning the pump filter
The filter is located beneath the pump
(SUNTEC) or in an appropriate
cartridge (DANFOSS). To clean it,
loosen the cover screws and remove it
(SUNTEC) or loosen the screw
(DANFOSS).
Check the tightness of the pump
cover and replace the seal if
necessary.
en
59