Operation
TEH control and safety programmer
R
- Reset button + Locked status
signal LED.
RJ45 - Connector for PC connection
(diagnostics, supplied
separately).
TEH
diagnostics tool kit
(not included)
LINE
C
1
2
-
-
1
No power
2
Power supply ON, no heat request
3
Heat request: heating of the nozzle
holder line engaged
4
Pre-ventilation: motor on,
ignition engaged
4' Stray light check
The TEH light oil control and safety pro-
grammer controls and monitors the
blown air burner. Thanks to the
programme managed by the micropro-
cessor, extremely stable times can be
obtained, regardless of the mains
voltage oscillations or the ambient tem-
perature. The control and safety pro-
grammer is designed for safe use in low
R
voltage conditions. If the mains voltage
falls below the minimum required value
(170 V), the control programmer deacti-
vates without signalling any error. As
soon as the voltage rises above 178 V,
RJ45
the programmer restarts automatically.
Symbols
3
4
4'
5s
< 400s
17s
5
Burner start-up: solenoid valve open,
flame ignition, safety time
6
Flame present, post-ignition time
7
Burner operation
8
End of heat request, the solenoid valve
closes, burner stops
07/2014 - Art. Nr. 4200 1057 7200
Lock and unlock
The control programmer can be locked
(put in anomaly mode) and unlocked
(anomaly removal) through the R
button, provided that the control pro-
grammer is powered at the mains
voltage.
device must be at zero voltage.
The control programmer must not be
opened or repaired.
Description
Waiting for a heat request
Waiting for nozzle holder line heating (for burners with
nozzle holder line heating)
Motor on
Ignition engaged
Flame present
5
6
5s
5s
8
9
Prior to mounting or dismantling
the control programmer, the
7
8
9
-
< 1s
-
End of heat request, the solenoid valve
closes, burner stops
Ready
en