General information
Contents
General information
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
Important warnings . . . . . . . . . . . . . . . . . . . . . . . . . .50
Burner description . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Operation
TEH control and safety programmer . . . . . . . . . . . . .53
Burner pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
Assembly
Burner assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
Electrical connections . . . . . . . . . . . . . . . . . . . . . . . .56
Checks prior to initial start-up . . . . . . . . . . . . . . . . . .56
Fuel supply line . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
Initial start-up
Configuration data . . . . . . . . . . . . . . . . . . . . . . . . . . .58
Air adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58
Burner adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . .59
Light oil pressure adjustment . . . . . . . . . . . . . . . . . . .59
Technical assistance
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . .61

Important warnings

The P1.xxx L/TEH (SV) burners are
designed for burning with low
emissions of pollutants derived from EL
heating oil, on the basis of the following
local regulations:
AT:
ÖNORM C1109: standard and
with low sulphur content
BE: NBN T52.716: standard and NBN
EN590: with low sulphur content
CH: SN 181160-2: EL heating oil and
biodiesel with low sulphur
content.
DE: DIN 51603-1: standard and with
low sulphur content.
Moreover, the burner structure and
operation conform to the EN 267
standard.
Assembly, initial start-up and
maintenance must be carried out
exclusively by authorised technical
personnel, in compliance with the
applicable directives and provisions.
Burner description
The P1.xxx L/TEH (SV) burners are
single-stage monoblock devices with
entirely automatic operation. They are
suitable for equipping all heat
generators complying with the EN 303
standard and/or air heaters conforming
to DIN 4794, DIN 30697 or EN 621
specifications compatibly with their
power range.
For every other use, authorisation from
ELCO is required.
In order to guarantee safe, non-
polluting and energy-saving operation,
the following standards must be
observed:
DIN 4755
Light oil control programmers on
heating systems.
EN 226
Connection of nebulising light oil
burners and blown air gas burners to
50
. . . . . . . . . . . . .52
heat generators.
EN 60335-1, -2-102
Safety electrical devices for domestic
use.
Installation site
The burner must not be operated in
rooms containing aggressive vapours
(e.g. hair spray, perchloroethylene,
carbon tetrachloride), substantial
amount of dust or high levels of air
humidity (e.g. laundry rooms).
A ventilation opening must be present,
with the following features:
DE: up to 50kW: 150 cm
2
for every successive kW:
+ 2.0 cm
.
2
CH: QF [kW] x 6= ...cm
;
2
min. 200 cm
.
2
Discrepancies may occur due to
municipal regulations.
The company shall not be held liable
for any damages deriving from the
following causes:
-
non-conforming use
-
defective assembly and/or repair by
the purchaser or third parties,
including the application of non-
original elements.
Delivery and operating instructions
The manufacturer of the combustion
plant must hand over the operating and
maintenance instructions to the plant
manager, at the latest during delivery of
the plant itself. These instructions must
be displayed in a visible manner in the
site where the heat generator is
installed. The address and telephone
number of the nearest technical
assistance centre must also be
indicated.
Warnings for the manager
The plant must be checked at least
once a year by a specialised
07/2014 - Art. Nr. 4200 1057 7200
Page
Declaration of conformity for light
oil burners
We,
ELCO
hereby declare, under our own
responsibility, that the following light
oil burners
P1.40 L/TEH (SV)
P1.70 L/TEH (SV)
P1.105 L/TEH (SV)
P2.130 L/TEH (SV)
conform to the following standards:
EN 267: 2010
EN 60335-1: 2008
EN 60335-2-30: 2006
EN 60335-2-102: 2007
EN 55014-1: 2008 + A1: 2009
EN 55014-2: 1998 + A1: 2001 + A2:
2008
These products are marked with the
CE mark in conformity to the
following directives:
2006/95/EEC Low Voltage Directive
2004/108/EEC EMC Directive
2006/42/EC Machinery Directive
Resana, June 2013
C. RENA
technician. In order to ensure regular
checks, it is advisable to stipulate a
contract for the maintenance of the
plant.