turck PS400 Série Mode D'emploi page 37

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Pressure Sensor Series PS400/PS500
10.1.1 Additional adjustment options in the sub-menu EF
Parameter Explanation
HI
Maximum value
memory
LO
Minimum value
memory
COF
Offset correction
dSP1
Switching delay
of SP1
dr1
Switching delay
of rP1
dSP2
Switching delay
of SP2
12
/0805
Hans Turck GmbH & Co.KG • D–45466 Mülheim an der Ruhr • www.turck.com
Option
Function
The highest pressure
value is stored in the
non-volatile memory.
The lowest pressure
value is stored in the
non-volatile memory.
Significant thermal
changes in the sensor
environment can lead to
zero shift. As a result,
the measuring value
displayed in a pressure-
free state will not accord
to zero. This drift can
be corrected. Adjustment
range: -5 to +5 % of the
measuring span
in increments of 0.1%
0 / 0.1 ... 50 s in
increments of 0.1 s
(0 = delay time not active)
0 / 0.1 ... 50 s in
increments of 0.1 s
(0 = delay time not active)
0 / 0.1...50 s in
increments of 0.1 s
(0 = delay time not active)