VOLTAGE PEAKS WHEN INDUCTIVE CONSUMERS ARE SWITCHED OFF
Voltage peaks when inductive consumers are switched off can lead to adverse
effects on electrical systems and may destroyed the switching contact.
•
Use commercially available standard RC combinations such as 0.1 µF/
100 Ohm for inductive consumers.
Failure to follow these instructions can result in injury or equipment dam-
age.
The output signal of the product is available via a voltage-free relay con-
tact (1 changeover contact).
1. The signal cable requires permanent installation.
2. Route the signal cable through the centre rubber piece into the black
base.
3. Connect the signal cable to the appropriate terminals with the designa-
tion "Release relay".