All manuals and user guides at all-guides.com
ATTENTION
Leaking connection due to failed pressing sequence
▶
Have any Geberit pressing collars that have not been closed
completely, as well as the adapter jaw and pressing tool,
inspected by an authorised repair shop.
▶
Replace any connections that have not been pressed
correctly. They must not be pressed again.
1
Press the Geberit pressfitting. → See operating instructions
for the relevant pressing tool.
2
After the pressing procedure, check that the Geberit
pressing collar is fully closed.
3
Open the Geberit adapter jaw and remove it from the
Geberit pressing collar.
4
Open the Geberit pressing collar and detach it.
4885212939-1 © 01-2020
968.751.00.0(00)
EN
35