Minimum distance between the cut-out and the
side wall.
Hob Control Type
Side knob control
Side knob control
Front knob control
Front knob control
* This size will be 60mm in models using 9-steps gas taps.
# Refer to the widht dimension in the technical specifications table of the user manual.
Room ventilation
All rooms require an openable window, or
equivalent, and some rooms will require a
permanent vent as well. The air for com-
bustion is taken from the room air and the
exhaust gases are emitted directly into the
room. Good ventilation is essential for safe
operation of your appliance.
Rooms with doors and/or windows which
open directly to the outer environment
The doors and/or windows that open dir-
ectly to the outer environment must have a
total ventilation opening of the dimensions
specified in the table below which is based
on the total gas power of the appliance
(total gas power consumption of the appli-
ance is shown in the technical specification
table of this user manual). If the doors and/
or windows do not have a total ventilation
Burner Plate Type
Metal
Glass
590 / 600 / 601 / 641 / 646
580 / 585 / 590 / 600 / 601 /
Metal / Glass
Metal / Glass
EN / 17
Y
Minimum distance between the rear edge of the
cut-out and the rear wall.
Hob Width# (mm)
580 / 610
641 / 646
750 / 751
opening corresponding to the total gas con-
sumption of the appliance as specified in
the table below, then there must definitely
be an additional fixed ventilation opening in
the room to ensure that the total minimum
ventilation requirements for the total gas
consumption of the appliance is achieved.
The fixed ventilation opening can include
openings for existing airbricks, extraction
hood ducting opening dimension etc.
Total gas consumption
(kW)
0-2
2-3
3-4
4-6
6-8
8-10
X (mm)
Y (mm)
100
60
100
50
170
50*
170
70
Min. ventilation opening
(cm2)
100
120
175
300
400
500