3006789-2024-09-12
1.1.3 Minimum EXact2 software version
1.1.4 Supply cables to DV controller
See menu 3.3
HMI: 3.10.0.0
AHU: 3.10.0.0
In EXact2 menu 3.3, "MC control" should be set to "4 modb."
Two new supply cables are delivered with the DV controller spare part.
If replacing an EC controller on the left side of the VEX280, supply cables on the left side must also be
replaced. This includes both the supply cable for the new DV controller and the supply cable for the
remaining old EC controller. Both cables should be connected directly to the automatic fuse in the
connection box. Drill new holes for the cables as according to the images below.
Please note that 2 earth wires (yellow/green) must be connected to both ends of the cable.
Added holes for cable: