Technical data
Power supply
Alternating voltage 230 V / 50 Hz, single-phase
Range approx. 195 V - 250 V / 50 – 60 Hz.
Output current:
Charging current max. 15 A,
(Charging current for
arithmetic average, electronically controlled according to
battery)
the charging characteristic curve
Output voltage:
Direct voltage 24 V
Charging process:
Automatic
Automatic switching:
Off at battery voltage 28,8 V charging current < 13,5 A.
(Main charging process)
Automatic switching:
Ten hours constant 28,8 V in the case of gel batteries.
(Post charging phase)
Four hours constant 28,8 V in the case of liquid batteries
Automatic switching:
Holding charge, constant at 27,6 V.
(Holding charge)
Temperature
The values of the automatic switching refer to a battery
dependent control
temperature of 20° C. When using a temperature sensor
(optional)
at the battery, these values vary as a function of the
battery temperature.
High temperature => Lowering of the threshold values.
Low temperature => higher threshold values.
Application:
Parallel operation, buffer operation, general charging
operation
Temperature:
Ambient temperature of -25° C to +35° C. During
operation, the housing may heat up to approx. 75° C.
Cooling:
By convection
Implementation:
According to Association of German Electrotechnical
Engineers regulations and the provisions of the
Instrument Safety Act.
Test labelling: