Télécharger Imprimer la page

Eaton Tripp Lite Serie Mode D'emploi page 13

Masquer les pouces Voir aussi pour Tripp Lite Serie:

Publicité

2 2 . . 7 7
L L E E D D I I n n d d i i c c a a t t o o r r s s
The Tripp Lite Series UPS system panel indicates the UPS status via the red and green LED indicators.
Table 2. LED Status Indicators
Description
Line Mode
Battery Mode
Battery Low
Line Mode Overload
Alert*
Battery Mode Overload
Alert**
Line Mode Overload
Fault*
Battery Mode Overload
Fault**
Replace Battery
Fault Condition
*Line Mode Overload Alert Condition - 110%±10%, goes to fault after 5 minutes; Overload Fault Condition - 120%±10%, goes to
**Battery Mode Overload Alert Condition - 110%±10%, shuts down in 5 seconds; Battery Mode Overload Fault Condition - 120%
Green LED
Red LED
On
Flashes every 10
seconds
Flashed solid every
second
On
Flashes
Off
Off
On
Flashes every minute
Off
fault immediately
±10%, shuts down immediately
Eaton Tripp Lite Series Cloud Connected UPS System User Guide 934927—Rev B
Alarm Tone
Off
Off
Off
Off
On
Beeps every second
Off
Beeps every 0.5 second
Off
Beeps every 0.5 second
On
Continuously beeps
Off
Off
Beeps every minute
On
Continuously beeps
LED Indicators
Notes
Operating in normal
line mode and the
battery is fully charged.
Set default is no alarm
until the event occurs
(e.g., battery low,
overload, etc.
1. Overcharge fault
2. Output short fault
7

Publicité

loading

Ce manuel est également adapté pour:

Avr750uncAg-0786