Heating mode:
Information requirements for heat pumps
Model(s):4×MASTER56CS;
Test matching indoor units form, non-duct : 4×MASTER56CS;
Outdoor side heat exchanger of air conditioner:air
Indoor side heat exchanger of air conditioner:air
Idication if the heater is equipped with a supplementary heater:no
If applicable:driver of compressor:electric motor
Parameters shall be declared for the average heating season,parameters for the warmer and colder heating seasoms are optional
Item
Symbol
P
Rated heating capacity
rated,h
Declared heating capacity for part load at indoor teperature 20℃ and
outdoor temperatures T
T
=-7℃
P
dh
j
P
T
=+2℃
dh
j
T
=+7℃
P
dh
j
T
=+12℃
P
dh
j
T
=bivalent
biv
P
dh
temperature
T
=operation
OL
P
dh
temperature
T
Bivalent temperature
biv
Degradation co-efficient
C
dh
for heat pumps(**)
Power consumption in modes other than "active mode"
Off mode
P
OFF
Thermosat-off mode
P
TO
P
Crankcase heater mode
CK
Capacity control
Sound power
L
WA
level,outdoor
GWP of the refrigerant
Contact details: EAS ELECTRIC SMART TECHNOLOGY P.I. San Carlos, Camino de la Sierra S/N Parc. 11 03370 Redován ESPAÑA
(*)
(**)If C
is not determined by measurement then the default degradation coefficient of heat pumps shall be 0.25
dh
Where information relates to multi-split heat pumps,the test result and performance data may be obtained on the basis of performance of the outdoor
unit ,with a combination of indoor unit(s) recommended by the manufacturer or importer
Value
Unit
kW
22.4
j
kW
12.113
kW
7.272
kW
5.825
kW
3.703
kW
12.113
kW
13.74
℃
-7
0.25
kW
0.04
kW
0.04
kW
0
Other items
variable
dB
78
2088
(100years)
kg CO
2 eq
40
Item
Seasonal space heating
energy efficiency
Declared coefficient of performance or gas utilisation
efficiency/auxiliary energy factor for part load at given outdoor
temperatures T
T
=-7℃
j
T
=+2℃
j
T
=+7℃
j
T
=+12℃
j
T
=bivalent temperature
biv
T
=operation temperature
OL
Supplementary heater
Back-up heating capacity(*)
Type of energy input
Standby mode
For air-to-air heat pump:air
flow rate,outdoor measured
Table.4
Symbol
Value
Unit
η
%
167.4
s,h
j
--
COP
3.22
d
--
COP
3.56
d
--
COP
6.76
d
--
7.76
COP
d
--
COP
3.22
d
COP
--
2.35
d
elbu
0
kW
P
kW
0.04
SB
3
9000
m
/h
V.1