American Standard Ultima Selectronic 6065.100 Instructions D'installation page 9

Publicité

SET DETECTION RANGE
D
(If Required); Fig. 13 y 14
Note: The detection distance is preset and ideal for most
installations. Should an adjustment be required, follow
the steps below.
1. Loosen SET SCREW (1) with 2.5mm Hex Wrench (2) in
back of FLUSH VALVE COVER (3). Fig. 13a.
2. Rotate COVER (3) to the right and pull off. Fig. 13b.
3. Turn COVER (3) over and disconnect CABLE (4) from
BATTERY HOLDER (5). Fig. 13.
4. Keeping hands away from the sensor detection area,
reconnect the SENSOR (4) and quickly place the COVER
(3) on the valve. Do not secure the COVER (3) at this time.
Note: You have 5 seconds to begin entering the program
code after power connection is made.
5. While the SENSOR CONTROL LED (5) is blinking slowly,
place your hand 1/4" - 1" (6mm-25mm) in front of the
sensor. Fig. 14.
6. When the LED (5) stops blinking and stays "ON" , move your
hand to the desired position from sensor and hold in place
until the LED (5) begins to blink again. Fig. 14.
Note: Detection Zone is 400 TO 800 mm (15-3/4" x 31-1/2")
(Factory Setting: 600 mm (23-5/8")
7. Once the SENSOR CONTROL LED (1) begins to blink
again, remove your hand from the detection zone.
When the flashing stops, the detection distance is set.
8. Replace and secure COVER (3) onto valve.
9. Actuate the FLUSH VALVE:
A) Cover sensor with hand for 10 seconds.
NOTE: Stand outside of sensor detection area.
B) Remove hand from in front of the sensor; unit will
flush in approximately 3 seconds.
Fig. 14
1
BLINKING LED
1/4"-1" (6mm-25mm)
Fig. 13
1
2
5
DETECTION ZONE
400 TO 800 mm (15-3/4" x 31-1/2")
(Factory Setting: 600 mm (23-5/8")
1
9
VIEW "A"
STANDARD BATTERY
3
VIEW "A"
4
BLINKING LED
M965646 REV. 2.6 (4/24)
6
3