Alert Code Alert Text
FAN ERR
1.2
Cont.
2.1
PUMP ERR
2.2
PUMP ERR
Description
Possible Causes & Remedies
The load on the
2. If an extension cord is being used, make sure it
fan is higher than
expected
3. Have a certified electrician inspect the wall outlet
The pump does not
1. Turn cooling mode to Max Cooling and listen for
appear to be running
as intended
2. Check for broken or pinched wires or connectors. If
3. Check the pump connector attachment to the
The load on the pump
1. If an extension cord is being used, make sure it
is higher than expected
2. Check if the pump inlet is clogged. Clean if needed.
ALERT CODES
meets the size and length requirements in the
Safety section of this manual. Remove/replace if
necessary.
circuit.
water circulation and look for proper media wetting.
If water is not circulating, disconnect power and
proceed to step 2.
wires are damaged do not attempt to repair, instead
replace the pump.
control module to ensure the fit is snug. Unplug and
clean out terminals if necessary. Plug in and recheck
pump operation. Replace the pump if necessary.
meets the size and length requirements in the
Safety section of This manual. Remove/replace if
necessary.