Cable Entry (Kle); Blanking Plug; Double Cable End Box - Cooper Crouse-Hinds CEAG GHG 745 22 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Fig. 8
2 x Apparatus holder size 3 for pipe
mounting, only horizontally
A=
Fastening holes for:
Plastic terminal box GHG 745
Plastic terminal box GHG 746, only vertically
Plastic terminal box GHG 749, only vertically
Fig. 9
Mounting parts, cable end box *
Fig. 10
Mounting cable end box *
14
9
10
12
4
1
Mounting plate
2
Self cutting screws
3
Mounting set M5
4
Fixing screws
5
Sealing sleeve
6
Seal
7
Perforated plates
8
Clamp ring
9
Enclosure base
10
Double cable end box - upper part
11
Double cable end box - base part
12
Fixing screws for cover
13
Cable bushings
14
Semi-clamp
Explosion protected terminal boxes made of
plastic or stainless steel type GHG 74.
A
(dimension X = 0 mm)
(dimension X = 267mm)
(dimension X = 540mm)
1
6.3
Cable entries (KLE)/
Blanking plugs
2
Generally, only certified cable entries and
blanking plugs may be used.
3
Flexible cables are to be used with
4
trumpet-shaped cable glands or other
suitable entries with additional pull-relief.
5
The mounting directives applicable to the
6
fitted cable entries are to be observed.
7
When using cable entries with a lower IP -
protection than that which applies to the
8
device (see technical data, page 7), the IP -
protection of the whole device will be
reduced.
In order to establish the minimum protection
1/2
category, unused holes have to be closed with
a certified blanking plug.
6
Care has to be taken that when fitting the
cable entries, sealing inserts appropriate to
the cable diameter are used.
11
In case of sealing inserts that are cut out, it
will have to be ensured that the insert is
8
properly adapted to the cable diameter.
13
In order to ensure the required minimum
protection category, the cable glands shall be
tightened down.
Overtightening might impair the protection
category.
Attention: When tightening the cap nut of
the (type ADL/ADE) metal cable entry, the
screwing is to be protected against
twisting by means of a suitable tool.
All vacant metric COOPER CROUSE-HINDS /
CEAG cable entries shall be closed with the
certified blanking plug for metric cable
entries.

6.3.1 Double cable end box

Mounting:
see fig. 9 and fig. 10
Unscrew the two fixing screws Item 4, and the
three fixing screws item 12 of the upper part
item 10, and remove the upper part.
Loosen the clamps item 14, of the strain-relief.
The cable sleeves item 13, have to be cut to
suit the cable diameter.
After fitting the cable, the cable sleeve item
13, is to be sealed by means of the respective
clamp ring item 8.
Finally, the upper part item 10, is fitted and
screwed down with the fixing screws item 4
and item 12, and the pull-relief item 14, is
again put in place.
The unused entry hole of the double cable
end box is to be closed with a sealing sleeve
item 5 (order No. GHG 740 1933 R0003).
Attention: In order to ensure that the
required minimum protection category is
withheld, it must be ensured that the seal
item 6, is in the correct position.
Cooper Crouse-Hinds GmbH
11
11
11
11
11