SolarEdge StorEdge SE2200H Guide Simplifie page 5

Onduleur monophasé avec technologie hd-wave et configuration setapp

Publicité

2
Wiring the System
Connecting System Components
Connect the system components as shown in the diagram below.
Pay attention to:
Cable types
DIP switch setup
If no Energy Meter is connected, terminate the inverter's RS485 bus by switching the left DIP switch ON.
LG Chem Battery
MAN-01-00642-1.2 StorEdge Single Phase Inverter Wiring and On Site Check Quick Guide
5-wire shielded twisted pair,
0.2 (0.2-1) mm² 600V/CAT5
ENABLE_H <> En
EN_GND <> G
RS485_H <> A+ and RS485_L <> B- on the same twisted pair
Inverter
Left DIP > OFF
B A G En
G <> G
B- <> B- and A+ <> A+
on the same twisted pair
Energy Meter
3-wire shielded twisted pair,
0.2 (0.2-1) mm² 600V/CAT5
DIP 2 > ON