- NTP Mode: one of three modes may be selected:
o Unicast: In Address IP 1, enter the IP address of the NTP server. In this case it is the clock that
calls the NTP server.
It is also possible to set up redundancy (if the first server does not respond, the second is queried,
and so on): for this purpose up to 5 server addresses may be entered.
The Periodicity field sets the frequency with which the clock queries the configured NTP
o Multicast: In this case, the NTP server broadcast the time on the multicast address that
was that given to it. The multicast address of the clients (reveivers) must be the same that the
one on which the server broadcasts.
By default, the Bodet products transmit or receive using the multicast address: 239.192.54.1
The multicast addresses are included between 224.0.0.0 and 239.255.255.255.
o By DHCP: Same mode as Unicast except that the addresses of the NTP servers are
gatherautomatically via the DHCP server (option 42 on the DHCP server).
The checkbox «continue to display time after synchronisation failure» is used to define the
behavior of the AFNOR output after synchronisation NTP failure during 48 hours :
■ The checkbox «continue to display time after synchronisation failure» in OFF, stop
AFNOR emission (configuration by default).
■ The checkbox «continue to display time after synchronisation failure» in ON, the clock
continues to broadcast AFNOR.
The Save buttons save the configuration data entered.
10
EN
servers.