ALL RADIO CODES FOR TOTAL OPENING CANCELLATION PROCEDURE
Cancellations can only be performed when gate is stationary.
1 - Set DIP 1 to ON and then DIP 2 to ON.
2 - LED DL12 flashes red for 10 s.
3 - Press and hold the PROG button for 5 s. Memory cancellation is indicated by two green
flashes of LED DL12 and 2 tones of the buzzer.
4 - LED DL12 flashes red again for 10 s and you can add new codes as shown above.
5 - Re-set DIP 1 to OFF and DIP 2 to OFF.
RADIO CODES MEMORY FULL INDICATOR (FOR TOTAL OPENING)
Indication is visible only when gate is stationary.
1 - Set DIP 1 to ON and then DIP 2 to ON.
2 - The LED DL12 flashes green 6 times when the memory is full (1000 codes). Now LED DL12
blinks red for 10 s enabling possible cancellation of all codes.
3 - Re-set DIP 1 to OFF and DIP 2 to OFF.
F - RADIO CODES PROGRAMMING PROCEDURE FOR PEDESTRIAN
OPENING
(1000 CODES MAX) - with radio module ACG8069
Programming can be done only when the gate is stationary.
1 - Set DIP 1 to ON and then DIP 3 to ON. DL12 flashes green for 10 s.
2 - Press the transmitter button (usually channel B) within the allotted 10 s. If the transmitter
is properly memorized LED DL12 blinks red and the buzzer emits a tone. The 10 s are
automatically renewed (DL12 flashes green) in order to memorize next transmitter.
3 - To finish programming wait 10 s, or press the PROG button briefly. The LED DL12 stops
flashing.
4 - Reset DIP 1 to OFF and DIP 3 to OFF.
REMOTE PROGRAMMING NEW REMOTE CONTROLS DEDICATED TO PEDESTRIAN OPENING
1 - Press the button on the valid remote control dedicated to pedestrian opening of the gate
3 times in rapid succession. The buzzer will sound 2 times for 1 second and the flasher will
flash for 4 seconds to signal the activation of the procedure.
2 - Immediately then press the same button once on the new remote control(s) you want
to register. The buzzer will sound 1 time to confirm the registration of each new remote
control. Wait 4 seconds for the procedure to exit. The flasher will turn off.
If you do not want to use this function, set DIP 3 to ON to deactivate it.
ALL RADIO CODES FOR PEDESTRIAN OPENING CANCELLATION PROCEDURE
Cancellation can only be performed when the gate is stationary.
1 - Set DIP 1 to ON and then DIP 3 to ON. LED DL12 flashes green for 10 s.
2 - Press and hold the PROG button for 5 s. Memory cancellation is indicated by two red flashes
of LED DL12 and two tones of the buzzer.
3 - The red LED DL1 remains active and you can add new codes as shown above.
4 - Reset DIP 1 to OFF and DIP 3 to OFF.
RADIO CODES MEMORY FULL INDICATOR (FOR PEDESTRIAN OPENING)
Indication is visible only when gate is stationary.
1 - Set DIP 1 to ON and then DIP 3 to ON.
2 - LED DL12 flashes green 6 times if the memory is full (1000 codes). LED DL12 blinks red for 10
s enabling possible cancellation of codes.
3 - Set DIP 1 to OFF and DIP 3 to OFF.
G - PROGRAMMING RADIO CODES FOR R-AUX RELAY
(1000 CODES MAX) - with radio module ACG8069
Programming can be done only when the gate is stationary.
1 - Set DIP 1 to ON, DIP 2 to ON and then DIP 3 to ON. DL12 flashes orange for 10 s.
2 - Press the transmitter button (usually channel C) within the allotted 10 s. If the transmitter
is properly memorized LED DL12 blinks green and the buzzer emits a tone. The 10 s are
automatically renewed (DL12 flashes orange) in order to memorize next transmitter.
3 - To finish programming wait 10 s, or press the PROG button briefly. The LED DL12 stops
flashing.
4 - Reset DIP 1, 2, 3 to OFF.
REMOTE PROGRAMMING NEW REMOTE CONTROLS DEDICATED TO THE R-AUX RELAY
1 - Press the button on the valid remote control dedicated to pedestrian opening of the gate
3 times in rapid succession. The buzzer will sound 3 times for 1 second and the flasher will
flash for 4 seconds to signal the activation of the procedure.
2 - Immediately then press the same button once on the new remote control(s) you want
to register. The buzzer will sound 1 time to confirm the registration of each new remote
control. Wait 4 seconds for the procedure to exit. The flasher will turn off.
If you do not want to use this function, set DIP 3 to ON to deactivate it.
RADIO CODES CANCELLATION PROCEDURE (FOR R-AUX RELAY)
Cancellation can only be performed when the gate is stationary.
1 - Set DIP 1 to ON, DIP 2 to ON and then DIP 3 to ON. LED DL12 flashes green for 10 s.
2 - During these 10 s press and hold the PROG button for 5 s. Memory cancellation is indicated
by two green flashes of LED DL12 and two tones of the buzzer.
3 - LED DL12 blinks orange again for 10 s and you can add new codes as shown above.
4 - Re-Set DIP 1, 2, 3 to OFF.
RADIO CODES MEMORY FULL INDICATOR (FOR R-AUX RELAY)
Indication is visible only when gate is stationary.
1 - Set DIP 1 to ON, DIP 2 to ON and then DIP 3 to ON.
2 - LED DL12 flashes green 6 times if the memory is full (1000 codes). LED DL12 blinks red for 10
s enabling possible cancellation of codes.
3 - Re-Set DIP 1, 2, 3 to OFF.
FUNCTIONING OF CONTROL ACCESSORIES
STEP-BY-STEP BUTTON (COM A+/START)
DIP 6 ON => It cyclically performs the commands open-stop-close-stop-open etc.
DIP 6 OFF => Opens the gate when closed. There is no effect if activated while opening. If
activated when gate is open, the gate closes. If activated while closing, the gate
re-opens.
OPEN BUTTON (COM A+/OPEN)
The button controls the opening movement when the gate is stationary. If activated while
closing, it re-opens the gate.
B.I.O. BUTTON - OPENS WITH CLOCK FEATURE (COM A+/B.I.O.)
This function is useful during peak hours, when vehicle traffic is slow (e.g. entry/exit of
workers, emergencies in parking or residential areas and, temporarily, for moving operations).
By connecting a switch and/or a daily/weekly clock to COM A+/B.I.O., you can open and keep
the automation open for as long as the switch is pressed or the clock remains active. When the
gate is open, all the commands are ignored.
Releasing the switch or at the end of the set time, the automation closes immediately.
Note: By activating the B.I.O. command for a time lower than the opening time (gate that has
not yet finished opening), even with an impulse, at the end of opening the gate will close
again after the automatic closing waiting time (fw 07.00 or higher .).
CLOSE BUTTON (COM A+/CLOSE)
Controls the closing movement when the gate is stationary.
TRANSMITTER
DIP 6 ON => It cyclically performs the commands open-stop-close-stop-open etc.
DIP 6 OFF => Opens the gate when closed. There is no effect if activated while opening. If
activated when gate is open, the gate closes. If activated while closing, the gate
reopens.
PEDESTRIAN OPEN BUTTON (COM A+/PED.)
Partial opening and closing control.
During pedestrian opening, pausing or closing, you can control the opening of any command
linked to the L1 board.
With DIP 6 you can choose the operation mode of the pedestrian push button.
DIP 6 ON => It cyclically performs the commands open-stop-close-stop-open etc.
DIP 6 OFF => Opens the gate when closed. There is no effect if activated while opening. If
activated when gate is open, the gate closes. If activated while closing, the gate
reopens.
FUNCTIONING OF SAFETY ACCESSORIES
PHOTOCELLS (COM A+/PHOT 1, COM A+/PHOT 2)
NOTE: the transit through the photocells is signaled by a buzzer tone
DIP 4 OFF => if an obstacle is placed in range of the photocells when the gate is closed, the gate
does not open. During operation, photocells work when opening (by starting the
opening movement only after the obstacle is removed) and closing (by starting
the reverse movement only after the obstacle is removed).