To set a timer for turning the unit on:
• Press TIMER to turn on the timer function.
• Press UP/DOWN repeatedly to set the delay ON time.
To set a timer for turning the unit off:
• Press TIMER to turn on the timer function.
• Press UP/DOWN repeatedly to set the delay OFF time.
To cancel the timer (when timer is activated):
• Press UP/DOWN repeatedly until display screen shows "00."
• Note: Pressing POWER will also disengage timer settings.
AUTOMATIC DEFROST
At low temperatures, frost may build up at the evaporator during operation. If
this happens, the unit will automatically start defrosting and the POWER
indicator light will blink. The defrost control sequence is as follows:
A. When the unit is operating in cooling or drying modes: If the ambient
temperature sensor senses the evaporator coil temperature is below 30°F,
the compressor will stop operating for 10 minutes or until the coil
temperature has risen to 45°F. Then, the unit will resume operation.
B. When the unit is operating in heating or drying modes: If the AC
compressor has been operating for 20 minutes or more, and the coil
temperature sensor senses that the evaporator temperature is below
104°F and that the ambient room temperature is below 66°F, the unit will
begin defrosting for 5 minutes and the power indicator will blink.
OVERLOAD PROTECTION
In the event of a power loss, there will be a 3-minute delay after power has
been restored before the compressor will resume operation.