Caractéristiques techniques
7.1 Tous les modèles d'appareils
Mode de protection et marquage Ex CSA, FM
Selon l'indice dans le numéro d'article
6DR5a.b-0cdef-g..h-Zjjj
a
b
0, 1, 2, 5, 6
1, 2, 3
0
1, 2, 3
1, 2, 3, 5, 6
5, 6
0, 1, 2, 3, 5, 6 5, 6
Le mode de protection Ex e / NI n'est pas autorisé en service avec Mechanic Limit Switches (MLS) 6DR4004-6K.
1)
94
Marquage Ex
CSA
c
 
D
Ex ec IIC T6...T4 Gc
NI Cl I Div 2 Gp A-D
Ex tb IIIC T100°C Db
DIP Cl II, III Div 1 Gp E-G
E
Ex ia IIC T6...T4 Gb
IS Cl I Div 1, 2 Gp A-D
E
Ex ia IIC T6...T4 Gb
IS Cl I Div 1, 2 Gp A-D
Ex ia IIIC T130°C Db
IS Cl II, III Div 1, 2 Gp E-G
F
Ex ia IIC T6...T4 Gb
IS Cl I Div 1, 2 Gp A-D
Ex ec IIC T6...T4 Gc
NI Cl I Div 2 Gp A-D
Ex ia IIIC T130°C Db
IS Cl II, III Div 1, 2 Gp E-G
G
Ex ec IIC T6...T4 Gc
NI Cl I Div 2 Gp A-D
K
Ex ia IIC T6...T4 Gb
IS Cl I Div 1, 2 Gp A-D
Ex ec IIC T6...T4 Gc
NI Cl I Div 2 Gp A-D
Ex ia IIIC T130°C Db
IS Cl II, III Div 1, 2 Gp E-G
Ex tb IIIC T100°C Db
DIP Cl II, III Div 1 Gp E-G
P
Ex db ia IIC T6...T4 Gb
XP IS Cl I Div 1 Gp C-D
Ex tb IIIC T100°C Db
DIP Cl II, III Div 1 Gp E-G
E
Ex db IIC T6...T4 Gb
XP Cl I Div 1 Gp C-D
Ex tb IIIC T100°C Db
DIP Cl II, III Div 1 Gp E-G
Marquage Ex
FM
 
1)
Cl I Zn 2 AEx ec IIC T6...T4 Gc
NI Cl I Div 2 Gp A-D
1)
Zn 21 AEx tb IIIC T100°C Db
DIP Cl II, III Div 1 Gp E-G
Cl I Zn 1 AEx ia IIC T6...T4 Gb
IS Cl I Div 1, 2 Gp A-D
Cl I Zn 1 AEx ia IIC T6...T4 Gb
IS Cl I Div 1, 2 Gp A-D
Zn 21 AEx ia IIIC T130°C Db
IS Cl II, III Div 1, 2 Gp E-G
Cl I Zn 1 AEx ia IIC T6...T4 Gb
IS Cl I Div 1, 2 Gp A-D
Cl I Zn 2 AEx ec IIC T6...T4 Gc
1)
NI Cl I Div 2 Gp A-D
1)
Zn 21 AEx ia IIIC T130°C Db
IS Cl II, III Div 1, 2 Gp E-G
Cl I Zn 2 AEx ec IIC T6...T4 Gc
1)
NI Cl I Div 2 Gp A-D
1)
Cl I Zn 1 AEx ia IIC T6...T4 Gb
IS Cl I Div 1, 2 Gp A-D
Cl I Zn 2 AEx ec IIC T6...T4 Gc
1)
NI Cl I Div 2 Gp A-D
1)
Zn 21 AEx ia IIIC T130°C Db
IS Cl II, III Div 1, 2 Gp E-G
Zn 21 AEx tb IIIC T100°C Db
DIP Cl II, III Div 1 Gp E-G
Cl I Zn 1 AEx db ia IIC T6...T4 Gb
XP IS Cl I Div 1 Gp A-D
Zn 21 AEx tb IIIC T100°C Db
DIP Cl II, III Div 1 Gp E-G
Cl I Zn 1 AEx db IIC T6...T4 Gb
XP Cl I Div 1 Gp A-D
Zn 21 AEx tb IIIC T100°C Db
DIP Cl II, III Div 1 Gp E-G
Notice de service, 02/2024, A5E03436620-AH
1)
1)
1)
1)
1)
1)
1)
1)
SIPART PS2 (6DR5...)