6.4
Installation conforme à UL
REMARQUE
En raison des exigences UL, le chapitre suivant est toujours en anglais, indépendam-
ment de la langue de la présente documentation. Les avertissements sont également
imprimés en français.
6.4.1
(Field wiring) Power terminals
Use 75 °C copper wire only.
6.4.2
Short circuit current rating
Suitable for use on a circuit capable of delivering not more than 5000 rms symmetrical
amperes when protected by 25 A, 600 V non-semiconductor fuses or 500 V minimum
25 A maximum inverse time circuit breakers.
Max. voltage is limited to 500 V.
6.4.3
Branch circuit protection
Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes.
WARNING - The opening of the branch-circuit protective device may be an indication
that a fault current has been interrupted. To reduce the risk of fire or electric shock,
current-carrying parts and other components of the controller should be examined and
replaced if damaged. If burnout of the current element of an overload relay occurs, the
complete overload relay must be replaced.
ATTENTION - LE DÉCLENCHEMENT DU DISPOSITIF DE PROTECTION DU CIR-
CUIT DE DÉRIVATION PEUT ÊTRE DÛ À UNE COUPURE QUI RÉSULTE D'UN
COURANT DE DÉFAUT. POUR LIMITER LE RISQUE D'INCENDIE OU DE CHOC
ÉLECTRIQUE, EXAMINER LES PIÈCES PORTEUSES DE COURANT ET LES
AUTRES ÉLÉMENTS DU CONTRÔLEUR ET LES REMPLACER S'ILS SONT EN-
DOMMAGÉS. EN CAS DE GRILLAGE DE L'ÉLÉMENT TRAVERSÉ PAR LE COU-
RANT DANS UN RELAIS DE SURCHARGE, LE RELAIS TOUT ENTIER DOIT ÊTRE
REMPLACÉ.
For maximum branch circuit protection see table below:
Non Semiconductor Fuses (currents are
Model
PHE1.B-A15-...
PHE2.B-A15-...
PHE3.B-B15-...
6.4.4
Motor overload protection
The devices are provided with load and speed-sensitive overload protection and ther-
mal memory retention upon shutdown or power loss.
SCCR: 5 kA/500 V
When protected by:
maximum values)
25 A/600 V
Notice d'exploitation – MOVIPRO
Installation électrique
Installation conforme à UL
Inverse-Time Circuit Breaker (currents
are maximum values)
25 A/500 V
®
PHE..B-A15-.1X0..B-00