Consignes d'installation
For devices with connection box PZM2xA-0075-D02-.., or PZM2xA-0150-D03-..
Model
MPX22A-..-0125.. (5.5 kW)
MPX22A-..-0160.. (7.5 kW)
MPX23A-..-0240.. (11.0 kW)
MPX23A-..-0320.. (15.0 kW)
For devices with connection box PZM2xA-0075-D02-.., or PZM2xA-0150-D03-..
Model
MPX22A-..-0125.. (5.5 kW)
MPX22A-..-0160.. (7.5 kW)
MPX23A-..-0240.. (11.0 kW)
MPX23A-..-0320.. (15.0 kW)
Motor overload protection
Multi motor application
Ambient temperature
Derating
Other ratings
Wiring diagrams
48
Notice d'exploitation – MOVIPRO
Standard fault current for group installation
Frame
size
Non-semiconductor fuses
(currents are maximum, vol-
2E
2E
3
3
Frame
size
Non-semiconductor Class J fuses (currents are maximum,
2E
2E
3
3
The devices are provided with load and speed-sensitive overload protection and ther-
mal memory retention upon shutdown or power loss.
The trip current is adjusted to 150 % of the rated motor current.
Coordination of branch-circuit short-circuit protective device and output tap conductors
shall be considered. Output circuit conductors sized smaller than the branch circuit
conductors shall comply with single motor tap rules of Article 430 of the NEC.
For ambient temperature rating refer to chapter "General technical data".
For derating refer to chapter "Selecting an inverter" of the Product Manual.
Type rating
Max. Altitude
For wiring diagrams, refer to chapter "Electrical Installation".
®
technology DSI
SCCR: 5 kA / 3 × 500 V
tages minimum values)
60 A / 500 V
60 A / 500 V
60 A / 500 V
60 A / 500 V
SCCR: 5 kA / 3 × 500 V
voltages minimum values)
40 A / 500 V
40 A / 500 V
40 A / 500 V
40 A / 500 V
Enclosed Type 1
2 000 m
Inverse time circuit breakers
(currents are maximum, vol-
tages minimum values)
60 A / 500 V
60 A / 500 V
60 A / 500 V
60 A / 500 V