Connection box line terminals:
Maximum Wire Size AWG 6. Conductors in the range 16 – 10 AWG are both solid and
stranded, and 8 AWG and larger are for stranded wire only.
Short circuit current rating
Suitable for use on a circuit capable of delivering not more than 5 000 rms symmetri-
cal amperes when protected by fuses or inverse time circuit breakers as described in
the tables below.
The max. voltage is limited to 500 V.
Suitable for motor group installation on a circuit capable of delivering not more than 5
000 rms symmetrical amperes when protected by fuses or inverse time circuit brea-
kers as described in the tables below:
The max. voltage is limited to 500 V.
Branch circuit protection
Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes (US) or Canadian Electrical Code, Part 1 (CA).
Standard fault current
For devices without connection box PZM2xA-0075-D02-.., or PZM2xA-0150-D03-..
Model
MPX22A-..-0125 ..(5.5 kW)
MPX22A-..-0160.. (7.5 kW)
MPX23A-..-0240.. (11.0 kW)
MPX23A-..-0320.. (15.0 kW)
For devices with connection box PZM2xA-0075-D02-.., or PZM2xA-0150-D03-..
Model
MPX22A-..-0125.. (5.5 kW)
MPX22A-..-0160.. (7.5 kW)
MPX23A-..-0240.. (11.0 kW)
MPX23A-..-0320.. (15.0 kW)
Frame
size
Non-semiconductor fuses
(currents are maximum, vol-
tages minimum values)
2E
50 A / 500 V
2E
60 A / 500 V
3
60 A / 500 V
3
60 A / 500 V
Frame
size
Non-semiconductor Class J fuses (currents are maximum,
2E
2E
3
3
Installation électrique
Consignes d'installation
SCCR: 5 kA / 3 × 500 V
Inverse time circuit breakers
(currents are maximum, vol-
tages minimum values)
50 A / 500 V
60 A / 500 V
60 A / 500 V
60 A / 500 V
SCCR: 5 kA / 3 × 500 V
voltages minimum values)
40 A / 500 V
40 A / 500 V
40 A / 500 V
40 A / 500 V