Connection To Power Supply - sauermann PE Série Manuel D'instruction

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 6
The PE range of Peristaltic pumps are designed to remove condensate water. They are particularly adapted
for use in Air Conditioning, Evaporator & Refrigerated cabinet applications.
Characteristics:
 Flow 6 l/h
 Max Discharge Head.: 12 m
 Max Suction Height: 2 m
 Power Supply: 230 V~ - 50/60 Hz
 Motor Power Level: 11 W
 IP 65
 Max Design Ambient Temperature: 50° C
0. SECURITY
0.1 In any case PE series peristaltic pumps have not to run continuously
0.2 Sauermann recommends to use a security system (Floating alarm ACC00601 NO/NC 10 Amp – 230
Vac (optional; see fig.8) or similar) allowing to stop the unit and prevent the overflowing whenever
an excessive amount of condensate is produced. The PE 5200 pump is equipped with a NC 8 Amp –
250 V contact allowing this function.
0.3 Sauermann does not accept any responsibility in case of not respect of these recommendation
1. INSTALLATION
Warning: Before carrying out any operation on the pump, make sure the installation is disconnected from
the power supply.
We recommend the pump be positioned with the suction & discharge spigots pointing downward.
 Installation with Mounting Bracket supplied (fig. 1)
-
Fasten the Mounting Bracket with the screw & rawlplug supplied.
-
Slide the pump body onto the bracket.
2. POWER SUPPLY (fig. 2 and 4)

2.1 Connection to power supply

Connect the pump to the power supply using a circuit breaker (not included) to standard IEC 345
on live & neutral.
2.2 Connection for model PE 5000 (Cooling only, compressor signal) (fig. 2)
English

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Pe 5000Pe 5100Pe 5200

Table des Matières