Appendix
A.1 I/O Connections and Wiring
Table A- 9
Input/Output Wiring (TB2) - 7ME39400AL04 Expanded I/O Module
Pin#
Signal
14
Chassis Ground
13
Chassis Ground
12
PG4
POS [+] Total TTL
11
PG3
POS [+] Total OC
10
PG2
NEG [-] Total TTL
9
PG1
NEG [-] Total OC
8
Io2 (-)
Isolated Return
7
Io2 (+)
4-20mA Output 2
6
Io1 (-)
Isolated Return
5
Io1 (+)
4-20mA Output 1
4
Vo2-
Ref. Ground
3
Vo2+
0-10 Volt Output
2
Vo1-
Ref. Ground
1
Vo1+
0-10 Volt Output
62
Definition
Chassis Ground
Chassis Ground
Totalizer Pulses, scalable
Flow meter process variables
assigned to individual outputs
under menu control.
4-20mA outputs also provide
a fault indication by dropping
to 2mA if assigned to flow
rate and under fault
conditions.
+5V
PG4
DPGEN_2-Ø2
2
4
TTL/CMOS
PG3
DPGEN_1-Ø2
1
+5V
PG2
DPGEN_2-Ø1
2
4
TTL/CMOS
PG1
DPGEN_1-Ø1
1
Description
Cable Shield Terminations
Cable Shield Terminations
POS [+] Total TTL
POS [+] Total OC
NEG [-] Total TTL
NEG [-] Total OC
System outputs assignable & scalable
to flow related parameters.
OC = Open Collector
FUS1010 IP65 NEMA 4X & IP66 NEMA 7 Quick Start
Operating Instructions, 01/2013, A5E03086486-AC
Function
Dual/Quad Path Only