10 - JUMPER SW15
The settings are stored during the rest phase (gate closed).
The default settings are highlighted in the boxes with grey background.
JUMPER
Function
TERMINAL 23
SW15
FUNCTIONING
11 - TRIMMER ADJUSTMENT
Trimmer
Default
FORCE
RUN
TIME
P.S.
TIME
(LEAF-DELAY TIME)
PAUSE
12 - PRELIMINARY CHECKS
Before powering the control unit, proceed with the following checks:
• Check the electrical connections; improper connection may be harmful to both the control unit and the operator.
• Check that the limit switches (if used) are in the correct position.
• Always provide for mechanical stops during opening and closing
• Set the DIP switches and trimmers for the desired operation.
Status
Description
N.C. devices are connected to STOP/EDGE input (23)
Resistive 8,2KOhm devices are connected to STOP/EDGE input (23)
Description
Turning clockwise adjusts (increases) the motor torque from 25% to 100%.
The first 3 seconds of movement take place with 100% of motor torque (force).
Set to the minimum (fully counter-clockwise), it will permit the RUN TIME LEARNING
PROCEEDURE with SLOW-DOWN to take place.
Turning clockwise, it adjusts the working time from 3.5 to 136 sec. and excludes learning
procedure and slow down.
Turning clockwise adjusts (increases) the closing delay time of leaf 1 with respect to leaf 2
from 0 to 20 seconds. The leaf-delay during opening is fixed at 2 seconds.
Set to minimum, the delays during both opening and closing will be cancelled
(version with 2 sliding gates), disables the opening release stroke DIP1_3 and the maintenance
of the hydraulic lock upkeep.
Turning clockwise adjusts (increases) the pause time from 3 to 103 seconds.
Automatic closing is disabled if adjusted to minimum. See operating logic DIP1_2.