Télécharger Imprimer la page

Napoleon BL56NTE Manuel D'installation page 13

Publicité

Les langues disponibles

Les langues disponibles

note:
The minimum clearances from the top of the horizontal vent pipe to combustible materials may be reduced from
3" (76mm) to 1" (25mm) in those installations with a minimum 38" (96.5cm) vertical vent rise made immediately
off the fi replace collar.
WARNING
!
Risk of fi re. Maintain specifi ed air space clearances to vent pipe and appliance.
The vent system must be supported every 3'(0.9m) for both vertical and horizontal runs. Use support ring assembly
W010-0067 or equivalent non-combustible strapping to maintain the minimum clearance to combustibles for both
vertical and horizontal runs. Spacers are attached to the inner pipe at predetermined intervals to maintain an even air
gap to the outer pipe. This gap is required for safe operation. A spacer is required at the start, middle, and end of each
elbow to ensure this gap is maintained. These spaces must not be removed.
This appliance uses a 5" (127mm) exhaust / 8" (203.2mm) air intake vent pipe system. Refer to the section
applicable to your installation.
For safe and proper operation of the appliance follow the venting instructions exactly. Deviation from the minimum vertical
vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent confi gurations, allow several
minutes (5-15) for the fl ame to stabilize after ignition. Although not a requirement, it is recommended for vent lengths that
pass through unheated spaces (attics, garages, crawl spaces) be insulated with the insulation wrapped in a protective sleeve
to minimize condensation. Provide a means for visually checking the vent connection to the appliance after the appliance is
installed. Use a fi restop, vent pipe shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.
The vent terminal may be painted with a high temperature paint to match exterior colours. Use an outdoor paint suitable for
400°F (200°C). Application and performance of paint is the consumer's responsibility. Spot testing is recommended.
note:
If for any reason the vent air intake system is disassembled; reinstall per the instructions provided for the initial
installation.
This appliance must be installed with a continuous connection of exhaust and air intake vent pipes. Utilizing alternate
constructions, such as a chimney as part of the vent system, is not permitted.
Use only Wolf Steel, Metal-Fab, BDM, Simpson Dura-Vent, or Selkirk Direct Temp venting components. Minimum and
maximum vent lengths, for both horizontal and vertical installations, clearances from vent pipes to combustibles and air
terminal locations as set out in this manual apply to all vent systems and must be adhered to. For Metal-Fab, BDM, Simpson
Dura-Vent, or Selkirk Direct Temp, follow the installation procedure provided with the venting components or on the website
for your venting supplier.
A starter adaptor must be used with the following vent systems and may be purchased through Wolf Steel or from the
corresponding supplier listed below:
Venting System
Manufacturer
SureSeal
Metal-Fab
Direct Vent Pro
Simpson DuraVent
Pro-Form
BDM
Direct Temp
Selkirk
Olympia Chimney
Ventis
and Venting
Connections made by means of an adaptor at the appliance, as well as the connection at the vent terminal must be sealed.
RTV sealant may be used on both the inner exhaust and outer intake vent pipe joints of all other approved vent systems, ex-
cept for the exhaust vent pipe connection to the appliance fl ue collar which must be sealed using the black high temperature
sealant Mill Pac.
For all vent systems is strongly recommend for all installations but required when power venting the appliance, that the outer
air intake joints are sealed using either high temperature silicone (RTV) or a suitable aluminum tape that covers each joint in
the vent system entirely around its circumference. This will ensure the best performance in every application and avoids per-
formance or condensation concerns that may occur in "tightly" constructed homes, particularly those in cold climates.
When using Wolf Steel venting components, use only approved Wolf Steel rigid / fl exible components with the following ter-
mination kits: wall terminal kit GD422-1, GD422R-2, ST58U-1 or 1/12 to 7/12 pitch roof terminal kit GD410, 8/12 to 12/12
roof terminal kit GD411, fl at roof terminal kit GD412 or periscope kit GD401 (for wall penetration below grade). With fl exible
venting, in conjunction with the various terminations, use either the 5 foot (1.5m) vent kit GD420 or the 10 foot (3.1m) vent kit
GD430.
3.0 venting requirements
Starter Adapter
Part Number
5DNA
Wolf Steel
W175-0170
Wolf Steel
N/A
BDM
5DT-AAN
Selkirk
Olympia Chimney
VDV-NA05-58F
and Venting
venting requirements
Supplier
Website
www.mtlfab.com
www.duravent.com
www.dalsinmfg.com
www.selkirkcorp.com
www.olympiachimney.com
W415-3036 / 05.07.21
EN
13

Publicité

loading

Ce manuel est également adapté pour:

Ascent linear serieBl56pte