Télécharger Imprimer la page

SFA Sanicondens Best Flat Notice De Service page 15

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 12
The connection of the detection
system to the safety system of the
connected appliance is mandatory.
The guarantee does not cover damage caused if
the alarm is not connected.
INSTRUCTIONS FOR QUALIFIED
PROFESSIONALS ONLY:
To connect the detection system, connect the other
set of cables, black and grey (see "Alarm" label),
to the appliance (refer to the instructions of the
appliance). See fig. 10
NOTE: It is possible to connect the detection
system to an external alarm (audible or visual,
from 1.5V to 230V) by changing the connection of
the detection system. Sanicondens® Best Flat is
controlled by a dry contact supplied NC (normally
closed). To connect the external alarm, this contact
must be changed to NO (normally open fig.11.3).
To do this, open the cover (fig. 11.1), unplug the grey
wire from its location and plug it to the free contact
above (fig. 11.2).
The maximum current admissible for
our detection system is 4 A.
To protect the electrical components in the
Sanicondens® Best Flat, once the alarm has been
triggered, any water continuing to fill the tank comes
out through the overflow outlets of the tank.
3.4 MAINS CONNECTION
Ensure the electricity is turned OFF
at the main switch board before
wiring to connector.
Connect the power cable K to the
Sanicondens® Best Flat (fig. 9) and then to the main
power.
The wires in the mains lead are coloured in
accordance with the following code: Brown=Line,
Blue=Neutral, Green/Yellow=Earth.
Comply with local installation requirements.
4. USE
4.1 FUNCTIONAL TEST
Before turning on the pump, make
sure you remove the protective lock
pin from the rear of the device. See fig. 5.
- Pour water into the tank.
- Check that the pump starts and stops when the
water level drops.
- Check that there are no leaks in the connections.
4.2 FILLING THE NEUTRALIZER COMPARTMENT
- Remove the cover from the neutralizer compartment
(fig. 7).
- Add the neutralizing granules into this compartment
(fig. 8).
- Reposition the cover and clip it in place.
Sanicondens® Best Flat is ready to use.
5. INTERVENTIONS
Disconnect electrical supply before
working on the unit!
5.1 MAINTENANCE (FIG 12)
Check the quality of the neutralizing granules
regularly.
Neutralizing granules need to be replaced at least
once a year. When replacing the granules, make sure
to clean the compartment as well.
5.2 TROUBLESHOOTING
INSTRUCTIONS FOR QUALIFIED PROFESSIONALS
ONLY:
Fault detected
Probable causes
The pump 
The pump is not 
doesn't start.
connected to the 
power supply.
The lock pin has 
not been removed.
The unit is not 
leveled.
Power outage.
Float blocked.
Condensates inlet 
pipe blocked.
The pump does 
Noon-return valve 
not lift.
blocked.
Discharge pipe 
blocked.
6. STANDARDS
Sanicondens® Best Flat conforms to the European
directive on low voltage.
7. DISPOSAL
The device must not be disposed of as
household waste and must be disposed of
at a recycling point for electrical
equipment. The device's materials and
components are reusable. The disposal of
electrical and electronic waste, recycling
and recovery of any form of used
appliances contribute to the preservation of our
environment.
8. GUARANTEE
Sanicondens® Best Flat is guaranteed for two years
for parts and labour from the date of purchase,
subject to installation, use and maintenance in
accordance with this manual.
15
EN
Action needed
Plug in the unit.
Remove the 
lock pin.
Check the unit 
with a leveling 
tool.
Check the main 
power.
Clean the tank.
Clean the inlet 
pipe.
Clean the valve.
Clean the 
discharge pipe.

Publicité

loading