Analog Value Representation for the Measuring Ranges
of the Analog Output Modules in SIMATIC S5 Format
Introduction
The tables in this section contain the digitized output ranges for the analog output
modules.
Special considerations when setting parameters in analog output modules
Note
When setting the parameters of substitute values, make sure these values meet
the S5 format. The four digits with the lowest value are to include a "0"; otherwise
you may experience parameter errors of the analog output modules.
Output Ranges for Voltage and Current: " 10 V, " 20 mA
Table 39
SIMATIC S5 Format: Output Ranges "10 V, "20 mA
Output Range
" 10 V
" 20 mA
0
0
11.76
23.5156
10.0098
20.0195
10.0000
20.000
0.00976
0.0195
0
0.000
–0.0098
–0.0195
–10.0000
–20.000
–10.0098
–20.0195
–11.7578
–23.5156
0
0
Product information
A5E00236831-04
Analog Value Representation for Measuring Ranges with SIMATIC S5
Units
(Deci-
(Deci-
(Deci
11 10 9 8 7 6 5 4 3 2 1 0 x x x x
11 10 9 8 7 6 5 4 3 2 1 0
mal)
w1205
0
1
0 0 1 0 1 1 0 1 0 1 x x x x Overflow
1204
0
1
0 0 1 0 1 1 0 1 0 0 x x x x Underrange
1025
0
1
0 0 0 0 0 0 0 0 0 1 x x x x
1024
0
1
0 0 0 0 0 0 0 0 0 0 x x x x Rated
1
0
0
0 0 0 0 0 0 0 0 0 1 x x x x
0
0
0
0 0 0 0 0 0 0 0 0 0 x x x x
–1
1
1
1 1 1 1 1 1 1 1 1 1 x x x x
–1024
1
1
0 0 0 0 0 0 0 0 0 0 x x x x
–1025
1
0
1 1 1 1 1 1 1 1 1 1 x x x x Underrange
–1204
1
0
1 1 0 1 0 0 1 1 0 0 x x x x
v1205
1
0
1 1 0 1 0 0 1 0 1 1 x x x x Underflow