Télécharger Imprimer la page

Siemens SIMATIC S5 Information Produit page 43

Masquer les pouces Voir aussi pour SIMATIC S5:

Publicité

Les langues disponibles

Les langues disponibles

Measuring Range for Thermocouple: Type L in _C
Table 31
SIMATIC S5 Format: Measuring Range Type L in _C
Measuring
Units
Range in
Range in
(Decimal)
(Decimal)
_C
> 1150
1151
1150
1150
901
901
900
900
1
1
0
0
–1
–1
–200
–200
< –200
–201
Measuring Range for Thermocouple: Type L in _F
Table 32
SIMATIC S5 Format: Measuring Range Type L in _F
Measuring
Units
Range in
Range in
(Decimal)
(Decimal)
_F
> 2102
2103
2102
2102
1653
1653
1652
1652
1
1
0
0
–1
–1
–328
–328
< –328
–329
Product information
A5E00236831-04
Analog Value Representation for Measuring Ranges with SIMATIC S5
Data Word
12 11 10 9 8 7 6 5 4 3 2 1 0 X E O
0
0
1
0 0 0 1 1 1 1 1 1 1 0 0 1 Overflow
0
0
1
0 0 0 1 1 1 1 1 1 0 0 0 0 Overrange
0
0
0
1 1 1 0 0 0 0 1 0 1 0 0 0
0
0
0
1 1 1 0 0 0 0 1 0 0 0 0 0
0
0
0
0 0 0 0 0 0 0 0 0 1 0 0 0
0
0
0
0 0 0 0 0 0 0 0 0 0 0 0 0 Rated range
1
1
1
1 1 1 1 1 1 1 1 1 1 0 0 0
1
1
1
1 1 0 0 1 1 1 0 0 0 0 0 0
1
1
1
1 1 0 0 1 1 0 1 1 1 0 0 1 Underflow
Data Word
12 11 10 9 8 7 6 5 4 3 2 1 0 X E O
0
0
1
0 0 0 0 1 1 0 1 1 1 0 0 1 Overflow
0
0
1
0 0 0 0 1 1 0 1 1 0 0 0 0 Overrange
0
0
1
1 0 0 1 1 1 0 1 0 1 0 0 0
0
0
1
1 0 0 1 1 1 0 1 0 0 0 0 0
0
0
0
0 0 0 0 0 0 0 0 0 1 0 0 0
0
0
0
0 0 0 0 0 0 0 0 0 0 0 0 0 Rated range
1
1
1
1 1 1 1 1 1 1 1 1 1 0 0 0
1
1
1
1 0 1 0 1 1 1 0 0 0 0 0 0
1
1
1
1 0 1 0 1 1 0 1 1 1 0 0 1 Underflow
Range
Range
41