TC4-1CH
Viewing and Adjusting Current Day Number
If the program sequence is activated, you can view and adjust the cur-
rent day number. If the change modifies the parameter settings, the
controller will operate according to the new parameter settings. The
controller does not display a current day greater than 99 even if it contin-
ues to operate with the current parameter settings.
Set the selection knob to PROGRAM. The current day number
flashes on the display.
Use the adjustment knob to adjust the current day number.
A
LARM OFFSETS
The user can define an upper and a lower offset from the set point to set
off alarm # 4. If the room temperature overruns the limits defined by the
two offsets, the alarm goes off. The relay connected to the alarm is
activated one minute later (to use the relay, see the wiring diagram in-
cluded with this manual).
Set the selection knob to ALARM OFFSETS. "LO" is displayed,
alternating with the current lower offset.
Use the adjustment knob to adjust the lower offset. Press the push-
button to store the value in memory.
"HI" is displayed, alternating with the current upper offset. Use the
adjustment knob to adjust the upper offset. Press the push-button to
store the value in memory.
An offset can range from 0.5
two offsets are set to 10
is defined for the alarm. If you do not require this function, set the offsets
to a high value.
20
TC4-1CH.rev.01
o
o
F to 40
F (0.3
o
o
F (5.6
C). A fixed hysteresis of 0.3
o
o
C to 22.2
C). Initially, the
o
o
F (0.1
C)