Installation; Prior To Installation - Jøtul F 100 ECO Série Manuel D'installation Et D'utilisation

Publicité

Les langues disponibles
  • FR

Les langues disponibles

3.3 Walls
Distance to wall of fl ammable material -
see fi g. 1
The stove must be installed with a CE approved fl ue.
The distance of the fl ue pipe to combustible materials must also
be observed.
Distance to combustible wall protected by
fi rewall
See fi g. 1
Distance to walls covered by a fi rewall
Firewall requirement
The fi rewall must be at least 100 mm thick and be made of
brick, concrete-stone or light concrete. Other materials and
structures with satisfactory documentation may also be used.
Non-combustible materials mean materials like brick, clinker,
concrete, mineral wool, cilicate plates etc (materials that do
not burn). Note! A short distance to non-combustible wall
may lead to desiccation and discoloration of paint and cause
cracking.
The stove must be set up so that the stove itself, the fl ue
pipe, and the chimney can all be cleaned.
Make sure that furniture and other household items are not
so close as to get dried up by the stove. Flammable materials
should not be placed within 1000 mm of the fi replace.
3.4 Ceiling
There must be a minimum distance of 700 mm to a combustible
ceiling above the fi replace.

4.0 Installation

Before installing the fi replace, check it carefully for any
signs of damage.
The product is heavy! Ask someone to help you when
positioning and installing it.
Ensure that air vents in the room where the fi replace is
located are not blocked.

4.1 Prior to installation

The standard product comes in one package
When the product is unpacked, take out the ashlip, smoke
outlet and bag of screws.
Fig. 3
1. Remove the transport screws.