TOP OF ENCLOSURE
(COMBUSTIBLE)
STEEL
STUD
FRAME
NON-COMBUSTIBLE
(1727mm)
MINIMUM
CEILING
96"
(2438mm)
MINIMUM
ENCLOSURE
HEIGHT
TOP OF
APPLIANCE
(711mm)
OPENING
MINIMUM
* Within the appliance enclosure a 7" (178mm) clearance between the top of the vent pipe and combustible
materials is required. All other clearances within the enclosure, including where the vent pipe exits the
enclosure are subject to 2" (51mm) to the sides and bottom and 3" (76mm) to the top for horizontal and 1"
(25mm) for vertical.
** See venting section.
IMPORTANT: THE FIRESTOP ASSEMBLY PROVIDED MUST BE USED WHEN THE VENT PIPES PASS
THROUGH ANY WALL OR ARE TERMINATED HORIZONTALLY.
COMBUSTIBLE
MINIMUM 7"
(178mm)
68"
28"
NON-COMBUSTIBLE
3"
(76mm)
2" (51mm)
FIRESTOP
ASSEMBLY
84" (2134mm)
PLUS RISE **
3"
(76mm)
29
EN
0" (0m) IF NON-
COMBUSTIBLE
FINISHING IS USED
SUCH AS BRICK
AND STONE.
MINIMUM
W415-1334 / 06.10.14