Installation and Operating Instructions
EN
Central ventilation units AIR1 XH
Connection of air quality sensors:
The power supply (24 V DC) must be connected according to the wiring diagram (see wiring diagram).
The signal cables are connected according to the wiring diagram via the analogue inputs AI2, AI3 and AI4.
Connection information:
• If a room temperature sensor is connected to analogue input AI2, only analogue inputs AI3 and AI4 are available for
air quality sensors.
• Up to 3 different or same types of sensors can be connected to a ventilation unit with 3 free analogue inputs. The
highest ventilation requirement has priority.
• If more than 3 sensors are connected, the signal converter AIR1-SK with 6 analogue inputs and one analogue out-
put is available. Only the same type of sensor can be connected to a signal converter.
An output of 56,7 W or 88,1 W is available for the connection of air quality sensors. However, this decreases depending
on additionally connected accessories.
Thus, the available 24 V power supply must be considered for the connection of sensors based on the table.
AIR1 XH 1000-5500: The available DC output for 24 V accessory components is 56,7 W.
Accessory (AIR1 XH 1000-5500)
AIR1-BE TOUCH
Controller
AIR1-BE ECO
Controller
Electrical auxiliary heater (contactor)
AIR1-ENH
AIR1-NH WW
Warm water auxiliary heater (valve)
Cold water cooling register (valve)
AIR1-KR KW
AIR1-JVK
Volume control dampers (2 x)
AIR1-ULK
Recirculation damper
CO2 sensor
AIR1/KWL-CO2 0-10V
AIR1/KWL-FTF 0-10V
Humidity/temperature sensor
Mixed gas sensor
AIR1/KWL-VOC 0-10V
AIR1-CO2 K
CO2 duct sensor
RMK
Duct smoke sensor
AIR1 XH 7000-8500: The available DC output for 24 V accessory components is 88,1 W.
Accessory (AIR1 XH 7000-8500)
AIR1-BE TOUCH
Controller
AIR1-BE ECO
Controller
AIR1-ENH
Electrical auxiliary heater (contactor)
AIR1-NH WW
Warm water auxiliary heater (valve)
Cold water cooling register (valve)
AIR1-KR KW
AIR1-JVK
Volume control dampers (2 x)
Recirculation damper
AIR1-ULK
CO2 sensor
AIR1/KWL-CO2 0-10V
AIR1/KWL-FTF 0-10V
Humidity/temperature sensor
Mixed gas sensor
AIR1/KWL-VOC 0-10V
AIR1-CO2 K
CO2 duct sensor
RMK
Duct smoke sensor
Required output
6 W
0,24 W
5,4 W
6 W
6 W
5 W (2 x 2,5 W)
1 W
0,6 W
0,6 W
0,6 W
2 W
0,6 W
Required output
6 W
0,24 W
19 W
6 W
6 W
5 W (2 x 2,5 W)
1 W
0,6 W
0,6 W
0,6 W
2 W
0,6 W