Installation and Operating Instructions
Central ventilation units AIR1 XH
2�4 Commissioning assistant (wizard)
The most important ventilation unit settings can be adjusted using the commissioning assistant (wizard) (except for
adjustment, emergency operation, time/date, timer). The controller will automatically open the commissioning assistant
during the initial commissioning and starts with the language selection.
Commissioning Assistant
If the settings are to be subsequently adjusted (except for language selection, time, temperature and ventilation set-
points), the commissioning assistant (wizard) must be called up again.
2�4�1 Menu overview Commissioning assistant (wizard)
Commissioning Assistant (for control unit AIR1 BE-ECO)
Ceiling units plate
Choose con guration
AIR1 XC 700
Floor units plate
Choose con guration
None
Floor units rotary
Choose con guration
None
Choose Language
English
External 0-10V
control
No
Control function-
Mode
->
Supply air control
SAF CAV setp
Ventilation-
Reduced: 150 m3/h
Mode
Normal: 400 m3/h
Constant air ow
Boost: 600 m3/h
Electrical
EAF CAV setp
Reduced: 150 m3/h
preheater
No
Normal: 400 m3/h
Boost: 600 m3/h
Supply lter type
ePM1 55% (F7)
Extract lter type
ePM10 50% (M5)
After heater type
None
Cooler type
None
Free cooling
(Night cooling)
Yes ->
Sensor-Type
Ventilation on
Rel. Humidity*
demand
CO2/mixed gas (VOC)*
No
*
Menus are only
Accept all settings
visible after
and activate the
the corresponding
application
sensor type has
No
been assigned to an
analog input.
Main-
menu
Start
after rst
power
supply
Supply air temp***
Setp: 22.0 °C
Neutral Zone
0.0 °C
outd temp activation
22 °C
Outd temp night
High: 18.0°C
Low: 10.0°C
Room temp min 18.0°C
Hour for start/stop
free cooling
Start: 0
Stop: 7
Time to block heat
output after
free cooling
60 Min
Outdoor sensor
placed in intake
channel
No
Minimal: 80
Boost: 100 %
Di :
16
Stop-time: 2
Minimal: 800 ppm
Boost: 1000 ppm
Di :
160 ppm
Stop-time: 2
34
***
Di erent temperature
Sub-menus depending on selected
Temperature control mode
Sensor-Type
AI2: Rel. Humidity**
%
Sensor-Type
AI3: mixed gas (VOC)
Std
Sensor-Type
AI4: CO2
Std
**
Analog input AI2 not available for air
quality sensors, if temperature-control
mode with room temperature
sensor selected
EN