Test schedule
IX Unit has sufficient protection from
corrosion, weather, vibration and
other interfering factors.
X Accumulations of dust or dirt not
excessive.
Checking correct functioning
1. Switch on unit and perform the following checks
according to the test schedule:
Test schedule
I Direction of rotation / air flow
direction
II Ensure correct power consumption
The rating current
( rating plate) may be higher or
lower depending on local condi-
tions (duct distance,
altitude, temperatures).
III Thermal safety is ensured by the
motor protection switch
system.
19 Cleaning, maintenance
Perform repeat checks (cleaning and mainte-
nance intervals) for ventilation systems in ac-
cordance with BetrSichV 2015 at least annually.
Only an electrician trained in explosion protec-
tion may undertake cleaning and maintenance.
The intervals should be determined by the operating
company in accordance with EN 60079-17 and may
be extended if a sufficient maintenance concept is
used – frequency depending on ambient conditions
and anticipated restrictions. Shorten the mainte-
nance intervals in the event of dust or a corrosive
atmosphere.
DANGER
!
Danger from electric shock. Before accessing
the connection terminals, release all power supply
circuits, protect against switching on again, ensure
unit is de-energised, earth and connect the EARTH
with active parts which are to be short-circuited,
and cover or make inaccessible adjacent energised
parts. Attach warning sign in clearly visible place.
Ensure that there is no explosive atmosphere.
CAUTION
!
Hot motor surfaces may result in skin burns if
touched. Do not touch hot motor surfaces. Wait
until the motor has cooled before undertaking
cleaning and maintenance work.
CAUTION
!
Danger of injury if there is no protection
against reaching / contact (protective grille) on
the uncovered air inlet/outlet. Fan may only be
operated with protection against reaching in
both sides.
NOTICE: Damage to the unit
Units with pre-installed line feedthrough to the
terminal box may be damaged if the connec-
tion line is pulled or the unit is lifted using the
line. Do not pull connection lines or lift the unit
using the lines.
Cleaning by electrician trained in explosion
protection
Regularly clean fan at appropriate intervals with
a damp cloth, especially after long periods out of
service. Clean fan at shorter intervals if you expect
layers of dust to accumulate on the impeller and
other parts of the fan.
8
D
N
S
Maintenance by electrician trained in explosion
protection
The fan should be regularly checked and main-
tained. In particular, ensure:
● unimpaired flow in the air channel.
● the effectiveness of the protective grilles.
● compliance with the permitted temperatures.
● quiet bearings. Bearing life of 40 000 hours,
depending on application.
● cables are secure in the terminal box.
● potential damage to terminal box, cable
screw-connections, sealing plugs and cables.
D
N
S
● secure routing of cables.
During regular safety checks (maintenance interval),
undertake a complete check in accordance with the
test schedules in Chapters 16, 17 and 18.
This involves checking the function of safety compo-
nents, air gap, power consumption, bearing noise,
damage and disproportional vibration (e.g. impeller
imbalance). Remove dirt and foreign particles.
Repairs
If unit components are worn, send fan to our factory.
Unit component replacements and/or repairs are
only permitted in the manufacturer's factory.
20 Fault rectification
 Chapter 11, Action to take in the event of a fault.
21 Disassembly and environmentally-
sound disposal
DANGER
!
Danger from electric shock. Before accessing
the connection terminals, release all power supply
circuits, protect against switching on again, ensure
unit is de-energised, earth and connect the EARTH
with active parts which are to be short-circuited,
and cover or make inaccessible adjacent energised
parts. Attach warning sign in clearly visible place.
Ensure that there is no explosive atmosphere.
● Only an electrician trained in and authorised
for explosion protection work may undertake
disassembly.
● Once they have reached the end of their useful
lives, dispose of units in an environmental-
ly-sound manner in accordance with local
requirements.
on
Instructions de montage et Mode
d'emploi – Ventilateurs hélico-
centrifuges pour gaines rondes
pour zones à risque d'explosion
Cet appareil a été fabriqué selon la directive ATEX
2014/34/UE (anciennement directive 94/9/CE) et
convient aux zones explosibles.
Lisez attentivement le présent mode d'emploi
avant le montage et la première utilisation du
ventilateur et suivez les instructions.
Les avertissements qu'il contient vous mettent en
garde contre les situations dangereuses entraî-
neront/pourraient entraîner la mort ou de graves
blessures (DANGER / AVERTISSEMENT) ou des
blessures légères/de moindre importance (PRU-
DENCE) dans la mesure où elles ne sont pas
évitées. ATTENTION signale des endommagements
possibles du produit ou de son environnement.
Conservez ce mode d'emploi pour une utilisation
ultérieure.
1 Illustrations
Fig. A : Dimensions, niveau de puissance
acoustique
Fig. B : Exemple d'installation :
1
Gaine d'air, à fournir par le client
2
Manchette flexible, en option
3
Réducteur
4
Bornier
5
Plafond, support
6
Pied de fixation, en option
7
Ventilateur pour gaine ronde
Fig. C : Grille de protection, en option
Fig. D : Schéma de branchement
Pour le sens de refoulement / sens de rotation 
Flèches sur le boîtier en plastique  Chapitre 17
2 Volume de fourniture
Ventilateur avec câble de raccordement et bornier
anti-explosion (câble de raccordement entièrement
câblé), les présentes instructions de montage et
mode d'emploi. Pour ventilateur de la série n° 
Plaque signalétique sur ventilateur. Déclaration de
conformité CE à la fin du présent mode d'emploi
3 Qualification du personnel d'installation,
de nettoyage, d'entretien et de réparation
Le montage, la mise en service, le nettoyage et l'en-
tretien doivent exclusivement être effectués par des
électriciens qualifiés et agréés dans le domaine
de la protection contre les explosions. Seule
l'usine de production est autorisée à réparer le
ventilateur.
Vous êtes un électricien qualifié dans le domaine de
la protection contre les explosions si, en raison de
votre apprentissage, votre formation professionnelle
ou votre expérience, vous pouvez exécuter en toute
compétence et en toute sécurité l'installation et les
branchements électriques conformément aux sché-
mas de branchement fournis et au présent mode
d'emploi. Par ailleurs, vous devez être en mesure
de reconnaître, d'évaluer et d'éviter les risques
d'ignition et d'explosion, les risques dus à une
installation incorrecte, à l'électricité, aux décharges
électrostatiques, etc.
.

Publicité

loading

Ce manuel est également adapté pour:

Rrk 200 exRrk 250 ex