7.3 Faults and their rectification
with room air control RB-ZF4
See Chapter 7.2.1. for the rectification
i
of fault messages at the RB-ZF4.
Fault: Fans do not operate.
Fault message:
All 3 LEDs at the RB-ZF4 flash.
Cause 1
No
power
supply
Cause 2
Control circuit
board faulty or
jumper
incorrectly
plugged.
There is a
defined voltage
< 1.7 V on the
plug pins,
on the supply
or exhaust air
side.
68
Rectification
Measure the supply
voltage to the supply
air and exhaust air
fan. (Terminal
and
(exhaust
air/supply air) on
control circuit board
A2), Chapter 7.2.2.
Press and hold the
▲ button for approx.
5 seconds.
If the fault is not
rectified, the fault
message appears
again after about 1
minute. If this
happens, replace the
control circuit board.
Rectification
Delete the fault
message according
to Chapter 7.2.1
before measuring.
Measure the supply
air and exhaust air
defined voltage
according to Chapter
7.2.2. This must be in
the range from 1.7 to
10 VDC.
Replace the control
circuit board
or correct the jumper
settings.
Cause 3
Rectification
Exchange "Exhaust
Motor board or
fan is faulty.
There is a de-
fined voltage of
If the fault persists,
1.7 to 10 V on
the plug pins,
on the supply
and exhaust air
Reinstall the
side. The value
is dependent
on the set
ventilation
level.
Cause 4
Rectification
Clean the air
Thermostat
TH 10 for the
protection of a
Deice the heat
hydraulic re-
heating register
in the supply air
has triggered,
because the air
channels are
closed/blocked
or the heat
exchanger has
iced up.
air" motor board or
"Supply air" motor
board.
replace the exhaust
air or supply air fan.
removed motor board
first. As a rule, this is
completely OK.
channels.
exchanger.