REFMATE operating instructions
for the reference temperature.
For best results use an insulate
cup, do not let the sensor tips
touch any ice cubes. Do not
touch or hold the sensor wires.
Prepare an ice
bath by mixing
water and ice.
Wait 15 min.
and mix.
Temperature
must settle at
0°C / 32 °F. Use
separate
accurate
thermometer
Temperature Calibration
In the navigation, go with
to
and press
Choose the
to carry out the field
calibration of the temperature
sensors. Choose temperature
calibration and press
To start the calibration, enter
the PIN. The PIN is 9-0-0-0
Press
when
Insert the K-type sensors into
the prepared ice bath.
Wait until the actual
temperature is stable. By
pressing
when
activated, the respective
temperature sensor is
calibrated. The calibrated
temperature is visible now
under Act.Temp. The former
temperature is visible under
Calib.Temp. LP/HP for your
reference.
Calibration is only possible if
Cal.Temp. and Calib. Temp
difference is below 5K.
Wrong calibration can be
deleted with
Cal.Temp. can be chosen
between -4 to 30°C / -25 – 86
°F.