6.1.6
Menu
16
REFMATE operating instructions
Field calibration with
reference pressure
Zeroing the pressure sensors
Press and hold
pressure can also be zeroed in
the menu with zeroing the
pressure and press
Pressure calibration
In the navigation, go with
to
and press
tab to carry out the field
calibration of the pressure
sensors.
To start the calibration, enter
the PIN. The PIN is 0-0-0-9
The device must not be
pressurised at this time!
Press
when
Connect the device to a
system with a defined
pressure.
Pressure range: 10–60 bar
The higher the calibration
pressure, the more accurate
the calibration!
Wait until the calibration
pressure corresponds to the
reference pressure. By clicking
the respective pressure
sensor is calibrated.
The
.
. Use the