11
11 Device Information
Device Information
1
Type and order code
2
Design
2.1
Model
2.2
Degree of protection according to EN 60 529 for compact devices
and heating components
2.3
Installation location
3
Performance data
3.1
Operating temperature limits:
Heating water flow/return flow
Air
3.2
Temperature spread of heating water (flow/return flow) at A2 / W35
3.3
Heat output / COP
3.4
Sound power level device / outdoors
3.5
Heating water flow with an internal pressure differential of
3.6
Air flow rate
3.7
Refrigerant; total filling weight
3.8
Output of electric heating element (second heat generator)kW
4
Dimensions, connections and weight
4.1
Device dimensions
4.2
Device connections to heating system
4.3
Air duct inlet and outlet (min. internal dimensions)
4.4
Weight of the transportable unit(s) incl. packing
4.5
Buffer tank volume
4.6
Buffer tank pressure rating
5
Electrical Connection
5.1
Nominal voltage; fuse protection
5.2
Nominal power consumption
5.3
Starting current with soft starter
5.4
Nominal current A2 W35 / cosϕ
6
Complies with the European safety regulations
7
Additional model features
7.1
Defrosting
Type of defrosting
Defrosting tray included
7.2
Heating water in device protected against freezing
7.3
Performance levels
7.4
Controller internal/external
1. See operating limits diagram
2. This data indicates the size and capacity of the system. For an analysis of the economic and energy efficiency of the system, other parameters, such as, in particular, the defrosting
capacity, the bivalence point and regulation, should also be taken into consideration. The specified values, e.g. A2 / W55, have the following meaning: External temperature 2 °C
and heating water flow temperature 55 °C.
3. The heat circulating pump is integrated.
4. See CE declaration of conformity
5. The heat circulating pump and the heat pump controller must always be ready for operation.
E-9
All manuals and user guides at all-guides.com
1
°C / °C
°C
2
at A-7 / W35
kW / ---
2
at A2 / W35
kW / ---
2
at A2 / W50
kW / ---
2
at A7 / W35
kW / ---
2
at A10 / W35
kW / ---
dB(A)
3
m³/h / Pa
m³/h / Pa
type / kg
H x W x L cm
Inch
L x W cm
kg
l
bar
V / A
2
A2 W35
kW
A
A / ---
WPL 60I
Compact
IP20
Indoors
Up to 55 / above 18
-20 to +35
8.0
5.8 / 2.7
7.5 / 3.3
7.0 / 2.5
9.3 / 3.9
9.8 / 4.1
- / -
0.8 / 2700
2500 / 20
R404A / 2.0
2.0
190 x 75 x 65
G 1'' internal/external
44 x 44
245
50
6
400 / 16
2.3
19.5
4.1 / 0.8
4
Automatic
Reverse cycle
Yes (heated)
5
Yes
1
Internal