How to adjust mechanical stops for both directions
Clockwise mechanical stop setting
1. Untighten the nut corresponding to clockwise mechanical stop
and turn the mechanical stop 2 turns back.
2. Drive the actuator to clockwise travel limit position.
3. Get the clockwise mechanical stop in contact with output
sleeve then turn it back of 1 turn.
4. Retighten nut to keep mechanical stop in position.
Counter-clockwise mechanical stop settings
5. Untighten the nut corresponding to counter-clockwise
mechanical stop and turn the mechanical stop 2 turns back.
6. Drive the actuator to the counter-clockwise travel limit
position.
7. Redo settings steps 3 & 4 for counter-clockwise direction.
Perform complete electrical valve opening and closing operations.
The motor must stop on the positions set in the software and not on
the mechanical stops.