5 COMMISSIONNING
This section describes the commissioning with the Control
panel, except otherwise mentioned.
You can set the same settings with App from the menu
Settings > Commissioning of Actuator on valve.
In order to access the actuator settings, control mode must
be set to Local mode.
5.1 Accessing the actuator menu
To be able to set the actuator software or check the warnings or
alarms, you need to access the actuator menu, either with Control
panel or BC App depending on which Local control you use.
It is your responsability to set the security of the Local
Commands (Control Panel or Smartphone Application) for
your process:
The default position of the Control selector button
should be on Remote
The Access Code of the actuator should have been
changed
The remote command "Local Command Inhibition" (from
DCS) should be active