How to install cable glands
For each cable entry used
1. Remove plug from the cable entry with 19mm (M16 entry)
or 23mm (M20 entry) open-
end wrench.
2. Separate sealing nut from
its cable gland.
3. Screw and tighten cable
gland in the cable entry.
4. Thread the sealing nut on
the cable and pass the
cable through the cable
gland.
Unused entries must be kept closed by their plug.
Terminal blocks
Both thermal protector and torque limit device must be integrated
into your control system in order to prevent potential damage to the
actuator or valve.
English
Terminal blocks are located on a
side of the electronic assembly
and
consists
terminals. There are 2 main
blocks: 1
st
is to connect power
supply, 2
nd
to connect command
and signaling.
Control terminals are 1-35 & 2-36
Power terminals (3Ph/1Ph)
• 3Ph: L1, L2, L3 with phase
correction
• 1Ph: L (Live), N (Neutral)