Télécharger Imprimer la page

HTW ADMIRA FST3-140ADM Manuel De L'utilisateur Et D'installation page 68

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 81
W
A
D
Outdoor Unit Dimentsion (mm)
W
H
D
681
434
285
700
550
275
770
555
300
800
554
333
845
702
363
946
810
420
958
1333
417
Refrigerant Piping Connection
When connecting refrigerant piping, do not let substances or gases other than the specified
refrigerant enter the unit. The presence of other gases or substances will lower the unit's capacity,
and can cause abnormally high pressure in the refrigeration cycle. This can cause explosion and injury.
Note on Pipe Length
Please check the elevation difference between the indoor unit and the outdoor unit, the length
of the refrigerant pipe, and the curved places (bend) of the pipe as following:
Elevation difference: no more than 10 M
Pipe length: no more than 20 M
Bends: no more than 5 places
A minimum pipe run of 3 metres is required to
minimise vibration & excessive noise.
H
B
Mounting Dimentsion (mm)
B
A
460
292
450
260
487
298
514
340
540
350
673
403
634
404
Rows of series installation
The relations between H, A and L are as follows
L
L ≤ 1/2H
L ≤ H
1/2H < L ≤ H
Can not be installed
L > H
H
27
A
25 cm / 9.8" or more
30 cm / 11.8" or more
L

Publicité

loading