8.4.2 GLACIAR75M and GLACIAR140M
DIP switch, buttons and digital display positions of uints.
ENC1
S1
S2
DSP1
Fig. 8-13 Display positions
8.4.2 GLACIAR90M and GLACIAR180M
DIP switch, buttons and digital display positions of uints.
S6
S5
S12
DSP1
Fig. 8-14 Display positions
S3
S4
DSP2
ENC2
POWER
ENC4
NET_ADDRESS
DSP2
8.4.3 DIP switch instructions
GLACIAR75M and GLACIAR140M
Table 8-5
ENC1
S1-1
S1-3
S3-1
S4
8.4.3 DIP switch instructions
GLACIAR90M and GLACIAR180M
Table 8-5
ENC2
ENC4
S5-3
S12-1
S12-2
21
0-F valid for uint address setting
on the DIP switches
0 indicates the master unit and 1-F
0-F
the auxiliary uints
(parallel connection) (0 by default)
Normal control
OFF
Valid for S1-1 OFF(factory default)
Remote control
ON
valid for S1-1 ON
OFF
S1-3
ON
S1-3
ON
S3-1
DIP switch for capacity selection
0011
(GLACIAR75M defaults 0011)
DIP switch for capacity selection
0111
(GLACIAR140M defaults 0111)
DIP switch for capacity selection
(GLACIAR90M defaults 2)
2
(GLACIAR180M defaults 6)
0-F valid for uint address setting
on the DIP switches
0 indicate master unit 0,
1 indicate auxiliary unit 1,
0-F
2 indicate auxiliary unit 2,...,
F indicate auxiliary unit 15.(parallel
connection)
Normal control
OFF
Valid for S5-3 OFF(factory default)
Remote control
ON
valid for S5-3 ON
ON
OFF
ON
V.1