Johnson GLACIAR Serie Guide D'utilisation page 107

Publicité

Les langues disponibles

Les langues disponibles

Table 13-2
Model(s):
Outdoor side heat exchanger of chiller:
Indoor side heat exchanger chiller:
Type:
Driver of compressor:
Item
Rated cooling capacity
Declared cooling capacity for part load at given outdoor
temperature T
j
T
= + 35°C
j
T
= + 30°C
j
T
= + 25°C
j
T
= + 20°C
j
Degradation co-efficient for chillers (*)
Off mode
Thermostat-off mode
Capacity control
Sound power level, indoors/outdoors
Emissions of nitrogen oxides
(if applicable)
GWP of the refrigerant
Standard rating conditions used:
Contact details
(*) If C
is not determined by measurement then the default degradation coefficient of chillers shall be 0,9.
dc
(**) From 26 September 2018.
Information requirements for comfort chillers
Symbol
Value
P
82.13
rated,c
P
82.13
dc
P
59.15
dc
P
37.36
dc
P
26.05
dc
C
0.9
dc
Power consumption in modes other than 'active mode'
P
0.090
OFF
P
0.700
TO
Other items
Variable
L
83
WA
NO
(**)
--
x
--
675
Low temperature application
JOHNSON
P.I. San Carlos,. Camino de la Sierra S/N, Parcela 11
03370 Redován - Alicante (SPAIN-ESPAÑA)
47
GLACIAR90M
Air to water
Water
Compressor driven vapour compression
Electric motor
Unit
Item
Seasonal space cooling
kW
energy efficiency
Declared energy efficiency ratio for part load
at given outdoor temperature T
kW
T
= + 35°C
j
kW
T
= + 30°C
j
kW
T
= + 25°C
j
kW
T
= + 20°C
j
--
kW
Crankcase heater mode
kW
Standby mode
For air-to-water
comfort chillers:
air flow rate, outdoor
measured
dB
For water / brine-to-
water chillers: Rated
mg/
brine or water flow
kWh
rate, outdoor side heat
input
exchanger
GCV
kg
CO
2
eq
(100
years)
Symbol
Value
Unit
η
174.55
%
s,c
j
EER
2.89
--
d
EER
4.09
--
d
EER
5.10
--
d
EER
5.91
--
d
P
0
kW
CK
P
0.090
kW
SB
--
35000
m
/h
3
--
--
m
/h
3
V.1