8.3.2MAIN PCB
1) Label descriptions are given in Table 8-3
45
44
43
42
41
40
39
38
37
36
35
34
33
Table 8-3
NO.
1
CN30 Input of three-phase four-wire power supply (fault code E1) Input of transformer, 220-240V AC
current. (only valid for the main unit) Three phases A, B and C of power supply should exist 120° among
them. If the conditions are not met, fault of phase sequence or phase lack may occur, and fault code will
be displayed. When the power supply returns to normal condition, fault is removed. Attention: phase lace
and phase dislocation of power supply are detected only in the early period after the power supply is
connected, and they are not detected while the unit is in operation.
2
CN12:Quick return oil solenoid valve
3
CN80:Injection solenoid valve of compressor system B
4
CN47:Injection solenoid valve of compressor system A
5
CN5:Water side heat exchanger heaters connection
6
CN40:Multi-function solenoid valve
7
CN13:Electric of water side heat exchanger heaters connection
8
CN41:Liquid bypass solenoid valve
9
CN42:Crankcase heater
10
CN6:Four-way valve
11
CN43:Crankcase heater
12
CN4/CN11:Electric heater of water flow switch
13
CN27:Three-way valve(hot-water valve,reserve)
14
CN86:SV2,Spray cooling valve(reserve)
15
CN25:Pump(220-240V control power supply )
1)After receiving start-up instruction, the pump will be started up instantly, and will maintain start-up state
always in the process of operation.
2)In case of refrigerating or heating shutdown, the pump will be shut down 2 minutes after all modules stop
operating.
3)In case of shutdown under the pump mode, the pump can be directly shut down.
46 47
32
31
30
28
29
Fig. 8-11 Main PCB of GLACIAR90M and GLACIAR180M
Detail information
1
27
24
22
20
26
25
23
21
18
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
19
18
V.1

Publicité

loading

Ce manuel est également adapté pour:

Glaciar75mGlaciar90mGlaciar140mGlaciar180m