Table 13-8
Information requirements for heat pump space heaters and heat pump combination heaters
Model(s):
Air-to-water heat pump:
Water-to-water heat pump:
Brine-to-water heat pump:
Low-temperature heat pump:
Equipped with a supplementary heater:
Heat pump combination heater:
For low-temperature heat pumps, parameters shall be declared for low-temperature application. Otherwise,
parameters shall be declared for medium-temperature application. Parameters shall be declared for average
climate conditions.
Item
Rated heat output
(3)
at Tdesignh = -10
(-11) °C
Seasonal coefficient of performance
T
= -7°C
j
T
= +2°C
j
T
= +7°C
j
T
= +12°C
j
T
= bivalent temperature
j
T
= operation limit temperature
j
For air-to-water heat pumps:
T
= – 15 °C (if TOL < – 20 °C)
j
Bivalent temperature (maximum +2°C)
Cycling interval capacity for heating
at T
= -7°C
j
(4)
Degradation coefficient
at T= -7°C
Cycling interval capacity for heating
at T
=+2°C
j
Degradation coefficient
(4)
at T= +2°C
Cycling interval capacity for heating
at T
= +7°C
j
(4)
Degradation coefficient
at T
= +7°C
j
Cycling interval capacity for heating
at T
=+12°C
j
Degradation coefficient
(4)
at T
= +12°C
j
Power consumption in modes other than active mode
Off mode
Thermostat-off mode
Standby mode
Crankcase heater mode
Other items
Capacity control
Sound power level, indoors
Sound power level, outdoors
Contact details
(1) For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to
the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to
the supplementary capacity for heating sup(Tj).
(2) If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
Symbol
Value
Unit
Prated
kW
=Pdesignh
151.7
SCOP
--
3.65
Pdh
133.5
kW
Pdh
86.1
kW
Pdh
52.8
kW
Pdh
57.3
kW
Pdh
133.5
kW
Pdh
kW
141.9
Pdh
kW
--
Tbiv
°C
-7
Pcych
kW
--
Cdh
--
--
Pcych
kW
--
Cdh
--
--
Pcych
kW
--
Cdh
--
--
Pcych
kW
--
Cdh
--
--
P
0.180
kW
OFF
P
1.400
kW
TO
P
0.180
kW
SB
P
0
kW
CK
Fixed/Variable
Variable
L
--
dB(A)
WA
L
92
dB(A)
WA
Name and address of the manufacturer or its authorised representative.
53
GLACIAR180M
Item
Symbol
Seasonal space heating
energy efficiency
Active mode coef. of
SCOP
performance
Net seasonal coef. of
SCOP
performance
T
= -7°C
j
T
= +2°C
j
T
= +7°C
j
T
= +12°C
j
T
= bivalent temperature
j
T
=operation limit temperature
j
For air-to-water heat pumps:
T
=–15°C (if TOL<–20°C)
j
For air-to-water HP :
Operation limit
temperature
(maximum-7°C)
Heating water
operating limit temperature
Cycling interval efficiency
COPcyc
at T
= +7°C
j
Cycling interval capacity for
COPcyc
heating at T
=+12°C
j
Cycling interval efficiency
COPcyc
at T
= +7°C
j
Cycling interval capacity for
COPcyc
heating at T
=+12°C
j
Supplementary heater (to be declared even if
not provided in the unit)
Rated heat output(3)
Psup
= sup(Tj)
Type of energy input
Outdoor heat exchanger
For air-to-water HP: Rated
Q
air flow rate
For water-to-water: Rated
Q
water flow rate
For brine-to-water: Rated
Q
brine flow rate
[yes]
[yes/no]
[yes/no]
[yes/no]
[yes/no]
[yes/no]
Value
Unit
η
%
s
143.0
--
on
--
--
net
--
COPd
2.23
--
COPd
3.46
--
COPd
5.23
--
COPd
6.18
--
COPd
2.23
--
COPd
--
2.12
COPd
--
--
TOL
°C
-10
WTOL
°C
--
--
--
--
--
--
--
--
--
--
kW
70000
3
m
/h
airsource
--
3
m
/h
watersource
--
3
m
/h
brinesource
V.1

Publicité

loading

Ce manuel est également adapté pour:

Glaciar75mGlaciar90mGlaciar140mGlaciar180m